Fig.8Cleaningductsystem
8Troubleshooting
Awarningtrianglewithtextinthedisplayindicatesanalarm.Turnmenuselectortothewarningtriangle
andpressconrmtwicetoviewthealarm.
8.1Alarmlist
AlarmExplanation
Dothefollowing
Fan
Indicateserroroneithersupplyor
extractairfan.
Thealarmisdisplayedinthecontrolpanel.
Checkthatquickconnectorsareconnectedforthe
bothfans.
Contactyourinstallationcompanyorplaceof
purchase.
EMT/Fr-
ost
Indicatestriggeredfrostprotection
(incaseofinstalledwaterheating
battery)ortriggeredoverheat
protection(incaseofinstalled
electricre-heaterbattery).
Atriggeredfrostprotectionalarmresultsinthe
following:
Bothfansstop.
Outdoorandexhaustairdampersclosed.
Watervalveopenscompletely(10Vsignalgoes
outtotheactuator).
Theunitwillrestartoncethewatertemperature
reaches+5°Cabovethesetfrostprotection
temperature.
Atriggeredoverheatprotection(EMT)givesanalarm
inthecontrolpanel.
Resetbypushingtheresetbutton.Seechapter6.
Iftheproblemcontinuescontactyourinstallation
companyorplaceofpurchase.
SAVEVTR200/BUserManual