Explanations
Flowcontrol
EAF
Setp1/1:1100
m³/h
Setp1/2:550
m³/h
Setthenormal(1/1)and
reduced(1/2)airowforthe
extractairfan
Outdoor
comp.Setp.1
—20°C=10m³/h
0°C=0m³/h
Act.Comp:0
m³/h
SettheEAFairow
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualairow
compensation.
Pressure
controlSAF
Actual:Pa
Setp.:Pa
Showstheactualexternal
pressureandsetpointforthe
supplyairfan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV)
Pressure
controlSAF
Setp1/1:250
Pa
Setp1/2:100
Pa
Settheexternalpressureset
pointfornormalspeed(1/1)
andreducedspeed(1/2)forthe
supplyairfan.
Outdoor
comp.Setp.1
—20°C=0Pa
10°C=0Pa
Act.Comp:0
Pa
SettheSAFpressure
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualpressure
compensation.
Pressure
controlEAF
Actual:Pa
Setp.:Pa
Showstheactualexternal
pressureandsetpointforthe
extractairfan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV)
TopvexSR09,11,TR09-15OperationandMaintenanceInstructions
207880
13
SystemairAB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Topvex SR 09 and is the answer not in the manual?

SystemAir Topvex SR 09 Specifications

General IconGeneral
BrandSystemAir
ModelTopvex SR 09
CategoryAir Handlers
LanguageEnglish

Related product manuals