Technical data
8.3 Unit Electrical Data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum
working temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
VLS/VLH/VLC/VLR BLN
Rated voltage
Max. absorbed power
Rated current
Max. current FLA
Max. start-up current LRA
External fuses
Max. cable section (*)
Exchanger Resistance
Rated voltage
Max. absorbed power
V/ph/Hz
kW
A
A
A
A
mm
2
V/ph/Hz
kW
60,0
88,0
148
271,0
200,0
3x95
69,6
100,0
156,0
280,0
200,0
3x95
80,8
112,0
186,0
350,0
250,0
3x120
96,4
120,0
172,0
357,0
250,0
3x120
105,2
142,0
193,0
378,0
250,0
3x120
112,0
160,0
210,0
433,5
250,0
3x120
130,0
172,0
239,0
486,0
315,0
3x185
148,0
184,0
268,0
515,0
315,0
3x185
524
400 (±10%) /3/50
230 (±10%) /1/50
130
604 704 804 904 1004 1104 1204
VLS/VLH/VLC/VLR LN
Rated voltage
Max. absorbed power
Rated current
Max. current FLA
Max. start-up current LRA
External fuses
Max. cable section (*)
Exchanger Resistance
Rated voltage
Max. absorbed power
V/ph/Hz
kW
A
A
A
A
mm
2
V/ph/Hz
kW
58,5
84,6
144,6
268,0
200,0
3x95
67,5
94,9
150,9
274,9
200,0
3x95
78,6
106,9
180,9
344,9
250,0
3x120
94,2
114,9
166,9
351,9
250,0
3x120
102,2
135,2
186,2
371,2
250,0
3x120
109,0
153,2
203,2
426,7
250,0
3x120
127,0
165,2
232,2
479,2
315,0
3x185
145,0
177,2
261,2
508,2
315,0
3x185
524
400 (±10%) /3/50
230 (±10%) /1/50
130
604 704 804 904 1004 1104 1204
VLS/VLH/VLC/VLR ELN
Rated voltage
Max. absorbed power
Rated current
Max. current FLA
Max. start-up current LRA
External fuses
Max. cable section (*)
Exchanger Resistance
Rated voltage
Max. absorbed power
V/ph/Hz
kW
A
A
A
A
mm
2
V/ph/Hz
kW
58,5
84,6
144,6
267,6
200,0
3x95
67,4
94,9
150,9
274,9
200,0
3x95
78,6
106,9
180,9
344,9
250,0
3x120
94,2
114,9
166,9
351,9
250,0
3x120
102,2
135,2
186,2
371,2
250,0
3x120
109,0
153,2
203,2
426,7
250,0
3x120
127,0
165,2
232,2
479,2
315,0
3x185
145,0
177,2
261,2
508,2
315,0
3x185
524
400 (±10%) /3/50
230 (±10%) /1/50
130
604 704 804 904 1004 1104 1204
VLS-GB.indd 59 17-06-2009 15:56:47

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir VLS Series and is the answer not in the manual?

SystemAir VLS Series Specifications

General IconGeneral
BrandSystemAir
ModelVLS Series
CategoryHeat Pump
LanguageEnglish

Related product manuals