Fine Tune Mode (Continued)
Symbol Description Used
In
Default Range User
Setting
Set Pump Override Time - (CSC
5352 Only) This setting should be
used with direct boiler
compensation or non-storage
Calorifier applications to dissipate
heat after demand.
Fine
Tune
Mode
15 0 to 59
Minutes
Set Low Outside Temperature
Frost Logic - (CSC 5352 Only)
Sets the action of the plant in
relation to low outside air
temperature. UK logic will start the
pump until the Hysteresis (+2°C)
has been cleared. European logic
will start the pump and control the
valve/boiler to the NSB setting until
the Hysteresis (+2°C) outside has
been cleared.
Fine
Tune
Mode
10 = UK
1 =
European
Low Space Temperature Setting
(CSC 5352 only if space sensor
fitted) Sets the temperature at
which point the heating will come on
in boost until the hysteresis (+2°C)
has been cleared. (If an adjustable
room sensor is used then this
setting must be set to –10°C to
remove frost protection. Failure to
do so may result in control
problems).
*or
If the INF setting = 3 then this
settings sets the max. Return
Temperature Ratio. A divisor of
100 is used for the max. Return
Ratio Setting, e.g. 83 = 0.83.
Fine
Tune
Mode
10 *or
83
–10 to
127°C
October, 03 CSC USER GUIDE
38 of 42

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the t.a.c. Satchwell Climatronic CSC5352 and is the answer not in the manual?

t.a.c. Satchwell Climatronic CSC5352 Specifications

General IconGeneral
Brandt.a.c.
ModelSatchwell Climatronic CSC5352
CategoryThermostat
LanguageEnglish

Related product manuals