16 (36), 0-004-7506-4 (EN) TAC AB, 2001-08-08
TAC Xenta OP Handbook 2 Connection and Basic Functions
To turn OFF the Xenta 100 mode
1 (Disconnect and then) connect the OP; wait for a couple of
seconds for the Base unit message to appear.
2 Press both keys
. and for about three seconds
simultaneously.
3 Select 10.OP mode menu.
4 Press
+
or
–
to set the Xenta 100 mode OFF and
press
.
5 Select the 1.Exit service mode menu and press
.
Press enter to
access Xenta 100
(wait)
Connecting to
Xenta Base unit
OP Service menu
1. Exit service mode
2. Keyboard test
3. Display test
.
10 OP mode
Change OP mode
Xenta 100 : OFF
Bindable : TAC
1. Exit service mode
Bindable “Bindable” is a LonWorks term, describing how the OP is connected
and addressed in the network. This, in turn, affects the mobility of the
OP.
Use
+
or
–
to select Bindable mode from the following.
• TAC OP movable. Two available addresses following each
TAC Xenta Base unit.
• INST OP permanently electrically connected to the network;
installed with a binding tool.
• MAN OP movable, the domain ID of the network has to be
programmed via
OP Service menu – 4.LON address
(communication is here limited to Base units on the same
channel).
For OP version 3.11 and earlier the following modes can be chosen.
• OFF OP movable. Two available addresses following each
TAC Xenta Base unit.
• ON OP permanently electrically connected to the network;
installed with a binding tool.
Confirm your choice by pressing
.