EasyManua.ls Logo

t.a.c. Xenta OP - Technical Data

t.a.c. Xenta OP
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TAC AB, 2001-08-08 0-004-7506-4 (EN), 31 (36)
TAC Xenta OP Handbook 5 Technical data
5 Technical data
Supply voltage (from TAC Xenta or external source)
............................................................... 24 V AC ±20%, 50/60 Hz
.........................................................................or 24 (20–30) V DC
Power consumption............................................................. max 0,5 W
With the display backlight on, in total........................... max 1,2 W
Ambient temperature:
Storage ................................................................. –20 °C to +50 °C
Operating ................................................................. ±0 °C to 50 °C
Humidity ..............................................max. 90% RH non-condensing
Display .................................................4×20 characters, alphanumeric
Mechanical:
Enclosure ........................................................................... ABS/PC
Dimensions (mm).......................................................... 144×96×32
Weight.................................................................................... 0,4 kg
Panel cutout (mm).........................................136 ± 0,5 x 91,5 ± 0,5
Enclosure rating:
Hand-held panel .......................................................................IP 20
Network communication:
Protocol........................................................... FTT-10, L
ONTALK
Communication speed........................................................ 78 kbit/s
Unit connection:
TAC Xenta 100.......................... via modular jack on Wall Module
TAC Xenta 300 .............................. modular jack or screw terminal
TAC Xenta 401 .............................. modular jack or screw terminal
TAC Xenta 901 .............................. modular jack or screw terminal
Standards:
Emission....................................................................... EN 50081-1
Immunity ...................................................................... EN 50082-1
Part number:
Operator terminal TAC Xenta OP ................................ 0-073-0907
Operator terminal TAC Xenta OP/RU ......................... 0-073-0923
Mounting kit panel TAC Xenta OP .............................. 0-073-0904