5. For load wires with a diameter greater than 11 millimeter divide each bus bar cover plug into
two separate parts by bending and breaking it along its separate grooves, as illustrated in
Figure 20. Insert only the rounded parts into the bus bar protection bracket and fix it to the
output cover using two SEMS screw. Insert output cover assembly through the cables as
illustrated in Figure 20.
Figure20:Three60V‐100VUnits,WireDiameter>11mm,OutputCoverAssembly
6. Assemble one lug on each bus bar using one hexagon bolt, two plain washers, one helical
spring-lock washer and one hexagon nut as illustrated in Figure 21.

Figure21:Three60V‐100VUnitsLugsAssembly
SeparateGrooves
BusBarProtection
Bracket
BusBar
CoverPlug
M3x8SEMSScrew,NickelPlated
Tighteningtorque:4.7‐5.7Lbf‐inch(0.53‐0.64Nm)
OutputCover
OutputCover
Assembly
Forrecommendedlugsrefer
to seriesSafety&
InstallationManual.
Notsupplied.
HexagonNut,M8,StainlessSteel
HelicalSpring
LockWasher,M
8
,StainlessSteel
PlainWasher,M
8
,StainlessSteel
M8x25HexagonBolt,StainlessSteel
Tighteningtorque:106‐132Lbf‐inch(12‐14.9Nm)