TECHNICAL MANUAL FOR
GENESYS
TM
10KW/15KW
Programmable DC Power Supplies
Document: 83
-
530
-
000 Rev
TDK
-
Lambda Americas Inc.
High Power Divisio
n
405 Essex Road, Neptune, NJ 07753
Tel:
(732) 922
-
9300
Fax:
(732) 922
-
9334
www.us.TDK
-
Lambda.com/HP

Table of Contents

Questions and Answers

  • L
    Lee FlynnAug 16, 2025
    What to do if TDK-Lambda Power Supply has no output and all displays are blank?
    • J
      Jennifer LawrenceAug 16, 2025
      If your TDK-Lambda Power Supply shows no output and the displays are blank, check if the AC power cord is defective and replace it if necessary. Also, verify that the AC input voltage is within the specified range and connect the power supply to an appropriate voltage source.
  • C
    Candace SmithAug 18, 2025
    What to do if TDK-Lambda GENESYS 10KW has no output and display indicates “OUP”?
    • J
      Jonathan NortonAug 18, 2025
      If your TDK-Lambda Power Supply displays “OUP” and has no output, it means the Over Voltage Protection circuit has been tripped. Turn off the AC power switch, then check the load connections. If you're using analog programming, verify that the OVP setting is not lower than the output voltage.
  • S
    ssharpAug 21, 2025
    Why TDK-Lambda GENESYS 10KW output is present momentarily but shuts off quickly and the display indicates “AC”?
    • J
      jeffrey32Aug 21, 2025
      If the output of your TDK-Lambda Power Supply appears briefly but then shuts off, and the display shows “AC”, it could be due to the AC source voltage sagging when a load is applied. Check the input AC voltage and ensure that you connect the power supply to an appropriate voltage source.
  • K
    kpageAug 25, 2025
    What to do if TDK-Lambda GENESYS 10KW output voltage will not adjust and front panel CV LED is on?
    • H
      Heather MyersAug 25, 2025
      If the output voltage of your TDK-Lambda Power Supply won't adjust and the front panel CV LED is lit, check if the output voltage is set above the Over Voltage Protection (OVP) setting or below the Under Voltage Limit (UVL) setting. Adjust the OVP or UVL settings so they do not restrict the output voltage.
  • T
    teresa38Aug 27, 2025
    What to do if TDK-Lambda Power Supply output is present momentarily but shuts off quickly and the display indicates “OUP”?
    • S
      stacey25Aug 28, 2025
      If the output of your TDK-Lambda Power Supply appears briefly, then shuts off, and the display indicates “OUP”, check if the power supply is configured to Remote sense. Inspect the positive and negative load wires to ensure they are securely connected.
  • M
    Michelle MasonAug 30, 2025
    What to do if TDK-Lambda GENESYS 10KW Power Supply output current will not adjust and front panel CV LED is on?
    • T
      Terry WilliamsAug 31, 2025
      If the output current of your TDK-Lambda Power Supply won't adjust and the front panel CV LED is on, it indicates that the unit is in constant voltage mode. Check the current limit and voltage settings.
  • M
    Michael BarnesSep 2, 2025
    How to fix poor load regulation on TDK-Lambda GENESYS 10KW Power Supply when the front panel CV LED is on?
    • K
      Kyle GreenSep 2, 2025
      If you're experiencing poor load regulation with your TDK-Lambda Power Supply and the front panel CV LED is on, ensure that the sensing wires are properly connected according to the User’s Manual instructions.
  • W
    wleSep 6, 2025
    Why TDK-Lambda GENESYS 10KW output voltage will not adjust and front panel CC LED is on?
    • O
      olsonwillieSep 6, 2025
      If the output voltage of your TDK-Lambda Power Supply won't adjust and the front panel CC LED is illuminated, the unit is likely in constant current mode. In this case, check the current limit setting and the load current.
  • J
    Jeremy JonesSep 8, 2025
    What causes large ripple present in TDK-Lambda GENESYS 10KW output and how to solve it?
    • T
      Thomas ReynoldsSep 9, 2025
      If there's a large ripple present in the output of your TDK-Lambda Power Supply, it could be due to the power supply being in remote sense or a high voltage drop on the load wire. Check the load and sense wire connections for noise and impedance effects, and minimize the voltage drop on the load wires.
  • N
    Nicole DavisSep 12, 2025
    What to do if TDK-Lambda Power Supply front panel controls are nonfunctional?
    • A
      Anthony GrantSep 12, 2025
      If the front panel controls on your TDK-Lambda Power Supply are not working, the power supply might be in Local-Lockout mode. To resolve this, turn off the AC power and wait until the display turns off. Then, turn the AC power back on and press the REM/LOC button on the front panel.

Summary

Technical Manual for Genesys 10 KW;15 KW Programmable DC Power Supplies

Warranty Information

Limitation of Warranty

Details exclusions and limitations of the warranty coverage.

Warranty Service Procedure

Outlines the procedure for obtaining warranty service.

Safety Instructions

Grounding and Safety Warnings

Explains grounding and output terminal safety precautions.

Safety Instructions: Environmental Conditions

Environmental Operating Conditions

Lists operating environmental conditions for the power supply.

Chapter 1: General Information

Serial Communication Control

Explains how to control the unit via serial port.

Introduction and Features

Provides a general overview and key features of the Genesys power supply series.

Parallel Operation Setup

Explains how to connect units in parallel for higher current.

Chapter 7: RS232 & RS485 Remote Control

Connecting Power Supplies to Serial Bus

Guides connecting power supplies to a serial bus.

Multi-Power Supply Serial Connection

Details connecting multiple supplies to a serial bus.

Serial Communication Data Format

Specifies data format, addressing, message end, repeat, checksum, acknowledge, error, backspace.

Command Set Description and Categories

Details command usage, categories, initialization, and ID control commands.

Output Control Commands (Part 1)

Lists commands for output control: PV, PV?, MV, PC, PC?, MC.

Output Control Commands (Part 3)

Lists commands for OVP, UVL, AST, SAV, RCL, MODE settings.

Status, Error, and SRQ Registers Overview

Explains status, error, and SRQ registers structure.

Configuration and Settings

Details default settings and configuration options for serial communication.

Configuration and Mode Settings

Details default settings, address, interface selection, and modes.

Communication Interface Protocol Overview

Outlines the communication protocol details.

Output Control Commands (Part 2)

Lists commands for output control: DVC?, FILTER, OUT, OUT?, FLD, FLD?, FBD, FBD?, FBDRST.

Global Output Commands

Lists commands that affect all supplies, like GRST, GPV, GPC.

Single Byte Commands Overview

Describes single byte commands and their categories.

Status Control Commands

Commands to control status registers.

Service Request: Enable and Event Registers

Explains SRQ enabling and event registers.

RS232;485 Connector Pinout

Details the rear panel RS232/485 connector pinout.

Error Messages and Commands

Details error messages, command sets, and single byte commands.

Chapter 8: Isolated Analog Programming Option

Isolated Programming & Monitoring Connector

Details the isolated programming and monitoring connector.

Specifications for Analog Options

Provides technical specifications for analog programming options.

Isolated Programming Connector

Details the connector for the isolated analog option.

Setup and Operating Instructions

Guides the user through setup and operation.

Chapter 9: Maintenance

Troubleshooting Guide

Guides users through diagnosing and resolving problems.

Troubleshooting Guide Overview

Guides problem diagnosis and resolution.

Chapter 2: Specifications

Output Ratings (10 kW and 15 kW)

Lists output voltage, current, and power ratings for models.

EMC Compliance

Details electromagnetic compatibility standards and tests.

Input Characteristics

Details input voltage, phase, current, and protection.

Remote Analog Control and Signals

Explains analog programming and monitoring signals.

Digital Programming and Readback

Covers digital control and data readback.

Protective Functions

Describes built-in protection features like OVP, UVL, and Foldback.

Chapter 3: Installation

Turn-On Checkout Procedure

Details the procedure for checking the power supply after turn-on.

Over Voltage Protection (OVP) Check

Describes how to check the Over Voltage Protection function.

Connecting the Load

Provides instructions for connecting loads to the output.

Remote Sensing Details

Explains the operation and use of remote sensing.

Under Voltage Limit (UVL) Check

Describes how to check the Under Voltage Limit function.

Local and Remote Sensing Configuration

Covers configuring for local or remote sensing.

AC Input Power Connection

Provides instructions for connecting AC power.

Foldback Protection Check

Describes how to check the Foldback protection.

Single Load Sensing Options

Explains local and remote sensing for single loads.

Chapter 4: Front and Rear Panel Controls and Connectors

Front Panel Controls and Indicators Overview

Details the controls and indicators on the front panel via diagram.

Front Panel Controls Details

Details specific controls like VOLTAGE, CURRENT, OUT, REM/LOC, FOLD.

Front Panel Controls Details (Continued)

Details OVP/UVL, PREV, FINE buttons, and ALARM/ON/OFF controls.

Rear Panel Connections and Controls Diagram

Diagram illustrating rear panel connections and controls.

Rear Panel Controls and Indicators

Details rear panel components like connectors, switches, and screws.

J1 Programming and Monitoring Connector

Details the J1 connector for programming and monitoring.

J1 Connector Terminals and Functions

Details J1 connector pins for ENA, COM, Local/Remote, VPGM, IPGM, VMON, SO, PS OK, IMON.

Front Panel Controls and Indicators

Details the controls and indicators on the front panel.

SW1 Setup Switch Functions

Explains the function of the SW1 setup switch.

Chapter 5: Local Operation

Under Voltage Limit (UVL)

Describes the Under Voltage Limit feature.

Safe Start and Auto-Restart Modes

Explains the power supply's start-up modes.

Series Connection for Increased Output Voltage

Details series connection for higher output voltage.

Series Connection for Positive;Negative Output Voltage

Details series connection for positive/negative output voltage.

Parallel Operation Setup

Explains how to connect units in parallel for higher current.

Daisy-Chain Connection

Explains how to connect units in a daisy-chain configuration.

Front Panel Locking Mechanism

Explains how to lock/unlock the front panel controls.

Front Panel Locking States

Describes states when the front panel is unlocked or locked.

Standard Operation Modes

Explains basic operating modes: Constant Voltage and Constant Current.

Over Voltage Protection (OVP)

Describes the Over Voltage Protection feature.

Setting UVL Level

Guides setting the UVL level.

Enable;Disable Control via J1 Connector

Details Enable/Disable control via the J1 connector.

Over Temperature Protection (OTP)

Describes the Over Temperature Protection feature.

Advanced Parallel Operation Setup

Explains advanced parallel operation setup.

Setting OVP Level

Guides setting the OVP level.

Foldback Protection

Describes the Foldback protection feature.

Setting Foldback Protection

Guides setting the Foldback protection.

Series Operation

Explains how to connect units in series.

Output ON;OFF Control

Explains how to control the output ON/OFF state.

Output Shut-Off (SO) Control via J1 Connector

Details SO control via the J1 connector.

Chapter 6: Remote Analog Programming

Remote Voltage Programming

Guides remote voltage programming of output voltage and current limit.

Resistive Programming of Output

Guides resistive programming of output voltage and current limit.

Remote Monitoring of Output

Explains how to monitor voltage and current remotely.

TDK-Lambda GENESYS 10KW Specifications

General IconGeneral
Output Power10 kW
Control InterfaceEthernet, RS-232, RS-485, USB
Input Frequency47-63 Hz
ProgrammingSCPI
CoolingForced air
Operating Temperature0°C to +50°C
Safety StandardsUL60950-1, EN60950-1, IEC60950-1
Protection FeaturesOvervoltage, Overcurrent, Overtemperature