Table 4
-
1: Front Panel controls and indicators
Nu
m
ber
Control/Indicator
Description
Section
13
OVP/UVL button
Over Voltage Protection and Under Voltage limit se
t
ting.
-
Press once to set OVP using VOLTAGE encoder (the cu
r-
rent display
shows “OUP”)
-
Press again to set the UVL using VOLTAGE encoder (the
current display shows “UUL”).
5.3
5.4
14
PREV button
Main function:
Press PREV to display the output voltage
and current limit setting. For 5 sec. the display will show the
setting an
d then it will return to show the actual output vol
t-
age and current.
Auxiliary function:
Front Panel Lock. Press and hold
PREV button to toggle between “Locked front panel” and
“Unlocked front panel”. The display will cycle b
e
tween
“LFP” and “UFP”. Releasi
ng the PREV button while one of
the modes is displayed selects that mode.
5.17
15
PREV indicator
Green LED, lights when PREV button is pressed
16
FINE button
Voltage and Current Fine/Coarse adjustment control. O
p-
erates as a toggle switch. In Fine mode,
the VOLTAGE and
CURRENT encoders operate with high resolution and in
Coarse mode with lower resolution (approx. 6 turns).
Auxiliary function:
Advanced Parallel Operation Mode
Setting.
5.15
17
FINE indicator
Green LED, lights when the unit is in Fine m
ode.
18
ALARM indicator
Red LED, blinks in case of fault detection. OVP, OTP Fol
d-
back, Enable and AC fail detection will cause the ALARM
LED to blink.
19
ON/OFF Switch
ON/OFF Switch