7.10 STATUS, ERROR AND SRQ REGISTERS
This section describes the various status error and SRQ registers structure. The registers can be read
or set via the RS232/485 commands. When using the IEEE option, refer to the User’s Manual f
Power Supply IEEE Programming Interface.
7 for the Status and Error Re
The fault Condition Register and the Status Condition Register are read only registers that the user
he condition of the supply. Refer to Table 7
8 for description of the Fault Condition
Register bits and Table 7
10: Fault Condition Register
The AC input returns to normal.
The power supply cools down.
The supply output is turned On by front
panel button or OUT 1 command.
The supply output is turned ON by front
panel button or OUT 1 command.
Rear panel J1 “Shut Off” condition r
The supply output is turned On by front
panel button or OUT 1 command.
Rear panel J1 Enable terminals closed.
11: Status Condition Register
Output is ON and the supply is not in
Output is ON and the supply is not in
One or more faults are ac
reporting is enabled (using “FENAxx”).
Fault Event Register cleared (FEVE?).
Front Panel or serial command).