Cascade
80
Output variables
Generator A - F demand
Status ON/OFF of generators A-H; selection of the switching outputs
Status stage 1 - 8
Status ON/OFF of demand stages 1-8
Hours run A - H
Issue of the current hours run of generators A-H
Delay timer, generator
Countdown of the current delay (after the first demand is switched
on)
Min. runtime ctr. A - H
The remaining minimum runtime
Rank generator A - H
Display of the current priority of the generator, factoring in the
generator change.
Cascade stage
Display of the current cascade stage
If a higher cascade stage is switched on before the lower stages, all preceding stages will
be switched on as well, subject to the delay. In other words, if only stage 4 switches on,
stages 1 4 will be switched on.
The stage is switched on immediately if the delay of a cascade stage has already expired
when that stage is switched on.
The parameter menu provides the option of resetting the hours run meters, individually or all
together.
PLEASE NOTE: The meter readings of the hours run meters are saved to the internal
memory every hour. Therefore, in the event of a power failure, no more than 1 hour of
metering can be lost.
When loading function data, you will be asked whether you want to apply the saved meter
readings (see manual Programming Part 1: General information).