LED display  Possible solutions 
ADC Voltage 
Error 
  Check the input voltage 
signal and the voltage on 
the control board. 
 
EEPROM  
Archiving Error 
  Reconnect and if the 
warning signal appears 
again, replace the circuit 
board. 
  Contact TECO for more 
information. 
 
Control Board 
Error 
  Replace the control 
board. 
 
Wrong Running 
Direction Error 
  Cancel the run command 
for another direction on 
the terminal of control 
board. 
 
PTC Signal  
Loss 
  Check if MT terminal and
    GND terminal are 
    connected. 
 
Parameters 
Locked 
  Correct password input at 
parameter 13-07 
 
Password 
Setting Error 
  Password input at the 
second time is the same 
as that at the first time 
when the password lock 
function enables. 
 
Operator 
Reading Error 
  Check if the inverter is 
normally connected to the 
operator. 
RDE* 
Operator  
Writing Error 
  Check the inverter’s 
firmware version/ control 
mode/ models 
WRE* 
Operator 
Verifying Error 
  Check if the inverter is 
normally connected to 
the operator. 
VRYE* 
Repeat Run 
Command 
  Cancel the run command 
in reverse direction from 
the external terminal.  
 
Operator Read 
Prohibit 
  Set parameter 16-08 to 1 
(Allow to read inverter 
parameters and save it 
to the operator).   
RDP* 
External 
Emergency 
Stop 
  Remove & shutdown the 
run command of external 
emergency stop and 
reset it to multi-function 
digital input.   
 
LED display  Possible solutions 
Zero Speed 
Stop Warning 
  Set up the frequency 
command. 
Overload of Air
Compressor 
  Check if the compressor 
load used is higher than 
the standard one.  
 
PID feedback 
signal loss 
  Check 23-19 setting. 
  Make sure correct 
installation and PID 
feedback signal. 
 
* RDE、WRE、VRYE、RDP warning signals are 
only displayed in LCD keypad. 
4.4 Auto-tuning Error 
When a fault occurs during auto-tuning of a 
standard AC motor, the display will show the 
“AtErr” fault and the motor stops. The fault 
information is displayed in parameter 17-11.  
 
Note: The fault contact output does not 
energize with an auto-tuning fault. 
Refer to Table 4.3 for fault information 
during tuning, cause and corrective 
action. 
 
Table 4.3 Auto-tuning fault and corrective 
actions
 
Error   Corrective action  
01 
Motor data input 
error.  
  Check the motor 
tuning data (17-00 to 
17-09). 
  Check inverter 
capacity 
02 
Motor lead to 
lead resistance 
R1 tuning error. 
  Check the motor 
tuning data (17-00 to 
17-09). 
  Check motor 
connection. 
  Disconnect motor 
load. 
  Check inverter current 
detection circuit and 
DCCTs. 
  Check motor 
installation. 
03 
Motor leakage 
inductance tuning 
error. 
04 
Motor rotor 
resistance R2 
tuning error. 
05 
Motor mutual 
inductance Lm 
tuning error. 
07 
Deadtime 
compensation 
detection error