49 
LED display  Possible solutions 
Communication 
Error 
  Replace the control board 
 
CF01 
Operator 
Communication 
Error 2
 
  Disconnect the operator and 
then reconnect. 
  Replace the control board 
 
CT Fault 
  Check input voltage signal 
and the voltage on the 
control board. 
 
Double 
Communication 
Error 
  Check only one 
communication mechanism 
is used.  
 
PTC Signal  
Loss 
  Check if MT terminal and 
GND terminal are connected.
 
OPR 
Disconnection 
  Check if the operator is 
disconnected or removed. 
 
FBLSS 
PID Feedback 
Signal Loss
 
  Check if the proportion of 
loss pressure (23-19) is set 
correctly.  
  Make sure the feedback 
sensor is installed correctly 
and PID feedback signal 
operates normally.   
 
 
SC 
Short Circuit 
  Check if the load is at correct
wiring. 
 
PF 
Protection Fault 
  Remove run command in 
multi-function digital input 
terminals. 
 
TOL 
External 
Overload 
  Check external overload. 
  Reset external overload of 
digital input. 
 
 
4.3 Warning / Self-diagnosis 
Detection Function 
When the inverter detects a warning, the 
keypad displays a warning code (flash).  
 
Note: The fault contact output does not 
energize on a warning and the inverter 
continues operation. When the warning is no 
longer active the keypad will return to its 
original state. 
 
When the inverter detected a programming 
error (for example two parameters contradict 
each other of are set to an invalid setting), 
the keypad displays a self-diagnostics code.  
 
Note: The fault contact output does not 
energize on a self-diagnostics error. While a 
self-diagnostics code is active the inverter 
does not accept a run command until the 
programming error is corrected. 
Note: When a warning or self- diagnostic 
error is active the warning or error code will 
flash on the keypad.  
 
Refer to Table 4.2 for and overview, cause 
and corrective action for inverter warnings 
and self-diagnostic errors.  
 
Table 4.2 warning / self-diagnosis and 
corrective actions 
LED display  Possible solutions 
OV 
(flash) 
 Over voltage  
  Increase deceleration time
  Reduce input voltage to 
comply with the input 
voltage requirements or 
install an AC line reactor 
to lower the input voltage. 
  Remove the power factor 
correction capacitor. 
  Use dynamic braking unit.
  Replace braking transistor 
or resistor. 
  Adjust speed search 
parameters. 
 
UV 
(flash) 
under voltage  
  Check the input voltage. 
  Check input wiring. 
  Check power source 
  Replace magnetic 
contactor 
  Replace control board or 
complete inverter. 
 
OH1 
Heat sink 
overheating 
  Check the ambient 
temperature of the 
inverter.  
  Check the fan or dust and 
dirt in the heat sink. 
  Check the carrier 
frequency setting. 
 
OH2 
(flash) 
Inverter over 
heating warning
  Multi-function input 
function set incorrectly. 
  Check wiring 
OT 
(flash) 
 over torque 
detection  
  Check over torque 
detection parameters (08-
15 / 08-16). 
  Check and reduce motor 
load, check and operation 
duty cycle.