A-1
Appendix-A Instructions for UL
Main Circuit Terminal Wiring
UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as specified by the
crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap.
The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco
representative or directly with the Teco sales department.
Closed-Loop Crimp Terminal Size
Drive Model
F510
Wire Gaug
mm
2
, (AWG)
Termina Crimp Termina
Tool Insulation Cap
R/L1
 
S/L2
 
T/L3
U/T1
 
V/T2
 
W/T3
Screws
Model No.
Machine No
Model No.
2003
2 (14)
M4
R2-4
Nichifu NH 1 / 9
TIC 2
3.5 (12)
R5.5-4
TIC 3.5
5.5 (10) TIC 5.5
2008 5.5 (10)
M4
R5.5-4 Nichifu NH 1 / 9 TIC 5.5
2015 14 (6)
M4
R14-6 Nichifu NOP 60 TIC 8
2030 38 (2)
M6
R38-6 Nichifu NOP 60 / 150H TIC 22
2050 80 (3/0) M8 R80-8 Nichifu NOP 60 / 150H TIC 60
2075 150 (4/0) M8 R150-8 Nichifu NOP 150H TIC 80
2125 300 (4/0)*2 M10 R150-10 Nichifu NOP 150H TIC 100
2175 152 (300)*2 M12 R150-12*2 Nichifu NOP 150H TIC 150
4003
2 (14)
M4
R2-4
Nichifu NH 1 / 9
TIC 2
3.5 (12)
R5.5-4
TIC 3.5
5.5 (10) TIC 5.5
4010 5.5 (10)
M4
R5.5-4 Nichifu NH 1 / 9 TIC 5.5
4020 8 (8) M6
R8-6
Nichifu NOP 60 TIC 8
4040 22 (6) M6 R22-6
Nichifu NOP 60 / 150H
TIC 14
4075 60 (2) M8 R60-8 Nichifu NOP 60 / 150H
TIC 38
4125 150 (3/0) M8 R150-8 Nichifu NOP 150H
TIC 80
4250 300 (4/0)*2 M10 R150-10 Nichifu NOP 150H
TIC 100
4300 203 (400)*2 M12 R200-12S*2 Nichifu NOH 300K TIC 200
4375 253 (500)*2 M12 R325-12S*2 Nichifu NOH 300K TIC 325
4425 253 (500)*2 M12 R325-12S*2 Nichifu NOH 300K TIC 325
Type 1
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.
PS : About 2175 and 4300~4425, please see additional data page.
Recommended Input Fuse Selection
Drive Model F510
Fuse Type
Manufacturer: Bussmann / FERRAZ SHAWMUT
Model Fuse Ampere Rating (A)
200 V Class Three-Phase Drive
2001 Bussmann 20CT 690V 20A
2002 Bussmann 20CT 690V 20A
2003 Bussmann 30FE
690V 30A
2005 Bussmann 50FE
690V 50A
2008 Bussmann 50FE
690V 50A
2010 Bussmann 63FE
690V 63A
2015 FERRAZ SHAWMUT A50QS100-4
500V 100A
2020
Bussmann 120FEE / FERRAZ A50QS150-4
690V 120A / 500V 150A
2025 FERRAZ SHAWMUT A50QS150-4 500V 150A
2030 FERRAZ SHAWMUT A50QS200-4 500V 200A
2040 FERRAZ SHAWMUT A50QS250-4 500V 250A
2050 FERRAZ SHAWMUT A50QS300-4 500V 300A
2060 FERRAZ SHAWMUT A50QS400-4 500V 400A
2075 FERRAZ SHAWMUT A50QS500-4 500V 500A
2100 FERRAZ SHAWMUT A50QS600-4 500V 600A
2125 FERRAZ SHAWMUT A50QS700-4 500V 700A
2150 Bussmann 170M5464 690V 800A
2175 Bussmann 170M5464