A-1
Appendix-A Instructions for UL 
■ Main Circuit Terminal Wiring 
UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as specified by the 
crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap.
 
 
The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco 
representative or directly with the Teco sales department.
 
 
Closed-Loop Crimp Terminal Size 
 
Drive Model 
F510 
Wire Gaug 
mm
2
 , (AWG) 
Termina Crimp Termina
Tool  Insulation Cap 
R/L1 
 
 S/L2 
 
 T/L3
 
U/T1 
 
 V/T2 
 
 
W/T3
 
Screws
Model No. 
Machine No
  Model No. 
2003 
2 (14)
M4
 
R2-4
Nichifu NH 1 / 9 
TIC 2
3.5 (12)
R5.5-4 
TIC 3.5
5.5 (10) TIC 5.5
2008 5.5 (10)
M4
R5.5-4 Nichifu NH 1 / 9  TIC 5.5
2015 14 (6)
M4
R14-6 Nichifu NOP 60  TIC 8
2030 38 (2)
M6
R38-6 Nichifu NOP 60 / 150H  TIC 22
2050 80 (3/0) M8 R80-8 Nichifu NOP 60 / 150H  TIC 60
2075 150 (4/0)  M8 R150-8 Nichifu NOP 150H  TIC 80
2125  300 (4/0)*2  M10  R150-10  Nichifu NOP 150H  TIC 100 
2175  152 (300)*2  M12  R150-12*2  Nichifu NOP 150H  TIC 150 
4003 
2 (14) 
M4
 
R2-4 
Nichifu NH 1 / 9 
TIC 2 
3.5 (12) 
R5.5-4 
TIC 3.5 
5.5 (10)  TIC 5.5 
4010 5.5 (10)
M4
R5.5-4 Nichifu NH 1 / 9  TIC 5.5
4020 8 (8) M6
R8-6
Nichifu NOP 60  TIC 8
4040 22 (6) M6 R22-6
Nichifu NOP 60 / 150H
  TIC 14
4075  60 (2)  M8  R60-8  Nichifu NOP 60 / 150H
 
TIC 38 
4125  150 (3/0)  M8  R150-8  Nichifu NOP 150H
 
TIC 80 
4250  300 (4/0)*2  M10  R150-10  Nichifu NOP 150H
 
TIC 100 
4300  203 (400)*2  M12  R200-12S*2  Nichifu NOH 300K  TIC 200 
4375  253 (500)*2  M12  R325-12S*2  Nichifu NOH 300K  TIC 325 
4425  253 (500)*2  M12  R325-12S*2  Nichifu NOH 300K  TIC 325 
 
 
◆Type 1 
 
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used. 
PS : About 2175 and 4300~4425, please see additional data page. 
 
Recommended Input Fuse Selection 
 
Drive Model F510 
Fuse Type
Manufacturer: Bussmann / FERRAZ SHAWMUT 
Model Fuse Ampere Rating (A) 
200 V Class Three-Phase Drive
2001  Bussmann  20CT 690V  20A 
2002  Bussmann  20CT 690V  20A 
2003  Bussmann  30FE
690V  30A
 
2005  Bussmann  50FE
690V  50A
 
2008  Bussmann  50FE
690V  50A
 
2010  Bussmann  63FE 
690V  63A 
2015 FERRAZ SHAWMUT A50QS100-4 
500V  100A 
2020 
Bussmann 120FEE / FERRAZ A50QS150-4
  690V  120A / 500V  150A
 
2025  FERRAZ SHAWMUT A50QS150-4  500V  150A
 
2030  FERRAZ SHAWMUT A50QS200-4  500V 200A
 
2040  FERRAZ SHAWMUT A50QS250-4  500V  250A 
2050  FERRAZ SHAWMUT A50QS300-4  500V  300A 
2060  FERRAZ SHAWMUT A50QS400-4  500V  400A 
2075  FERRAZ SHAWMUT A50QS500-4  500V  500A 
2100  FERRAZ SHAWMUT A50QS600-4  500V  600A 
2125  FERRAZ SHAWMUT A50QS700-4  500V  700A 
2150  Bussmann  170M5464  690V  800A 
2175  Bussmann  170M5464