11
3.5 Wiring Diagram CVP Series Inverter
Wiring diagram I:
(
MCCB
L1(R)
AC
Power
source
S1
S2
S3
FM+
P
P
+
R1A
Multifunctional output terminals
250VAC/1A (30VDC/1A)
200V: Class 3 ground
400V: Special ground
T1(U)
T2(V)
T3(W)
PE
R1C
R1B
R2B
R2A
COM
S4
S5
DC
reactor
Braking
Resistor(note1)
L2(S)
L3(T)
( (
ON-OFF
Burst absorber
S6/AI2
10V
AIN
COM
-
COM
MC
Install fast
action fuse
Magnetic
contactor
Molded-case circuit breaker
TM2
CON 2
RS485
RS232
Memory Card
(Option Card)
Digital
Control
panel
CON1
V
I
SW2 SW3
NPN
PNP
SW1
SW2: AIN 0~10V/0~20mA selective
SW3: S6/AI2 0~10V/0~20mA selective
or 2~10V/4~20mA (after Ver.2.3)
I POSITION: 0~20mA signal
V POSITION: 0~10V signal
SW1: NPN/PNP selective
Forward/stop or run/stop
Reverse/stop or reverse/forward
Speed control
Common point for PNP input
Common point for NPN
Reset /Error recovery
(Multifunction input terminal)
Frequency indicator
device
+
-
Frequency indicator
0~10VDC
Multifunction input terminal
P
P1
BR
Power
output
FM
Induction
motor
24V
PE
Power
input
MC
Note 1: Please refer to description of main circuit terminals (P1, BR) and specification of
braking resistor for value selection.
Note 2: Above wiring diagram refers for 0.4~1.5KW at 220V and 0.75~1.5KW at 440V.