EasyManua.ls Logo

TECO JNTHBCBA0001BEAU - 3.7 Description of Terminals Troubleshooting Inverter

TECO JNTHBCBA0001BEAU
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
3.7 Description of Terminals Troubleshooting Inverter
Descriptions of main circuit terminals
Symbol Description
R / L1 ( L )
S / L2
T / L3 ( N )
Main power input Single-phase: L/N
Three-phase: L1/L2/L3
P1
BR
Braking resistor or connecting terminal: Used in cases where the
inverter frequently disconnects due to large load inertia or short
deceleration time (refer to specifications of braking resistor)
P1/ P
DC reactor connecting terminals
For
220V:0.5~10HP,
440V:1~15HP
B1/P
B2
-
Ө
z B1/P- Ө: DC power supply input
B1/P-B2: External braking resistor
For 220V: 15~20HP and 440V: 20HP
-
z - Ө : DC power supply input or
External braking unit.
For 220V: 25~40HP and 440V: 25~75HP
U / T1
V / T2
W / T3
Inverter outputs
y Do not remove the P-P1 jumper if there is no DC reactor connected.
Descriptions of
CVP control circuit terminals
Symbol Description
R2A
R2B
Multifunctional terminal – Normal open
R1C
Common contact
R1B
Normal close contact
R1A
Normal open contact
Multifunctional output
terminals
Contact rated capacity:
(250VAC/1A or 30VDC/1A)
10V Frequency knob (VR) power source terminal (pin 3)
AIN
Analog frequency signal input terminal or multifunction input terminals S7 (H level:>8V, L
level:<2V, PNP only)
24V
Common contact for S1~S5 (S6, S7) in PNP (Source) input. Shift to PNP position (refer to
wiring diagram) of SW1 when used PNP input
COM
24G
AGND
1. Common contact and analog input /output signal for S1~S5 in NPN (Sink) input.
Shift to NPN position (refer to wiring diagram I) of SW1 when used NPN input.
2. AGND for AIN,
A
I2 and FM+ (analog input /output signal) & 24G for S1~S6 (digital input
/output signal in NPN (Sink) input). Shift to NPN position (refer to wiring diagram II) of SW1
when used NPN input.
FM+
The positive analog output for multifunction, the signal for output terminal is 0-10VDC (below
2mA).
S1
S2
S3
S4
S5
Multifunctional input terminals
S6
1. Multifunction input terminals (Digital terminal H level:>8V, L level:<2V, PNP only) or analog
input terminal AI2(0~10Vdc/4~20mA)
2. The V2.9 version (contains) above the edition, S6 only is the Multi-function input terminal
use, AI2 have replaced S6 to take analog input use. (Above wiring diagram refers for
2.2~30KW at 220V and 2.2~55KW at 440V only.)

Table of Contents