15 
3.7 Description of Terminals Troubleshooting Inverter 
Descriptions of main circuit terminals 
Symbol  Description 
R / L1 ( L ) 
S / L2 
T / L3 ( N ) 
Main power input  Single-phase: L/N         
Three-phase: L1/L2/L3 
P1 
BR 
Braking resistor or connecting terminal: Used in cases where the 
inverter frequently disconnects due to large load inertia or short 
deceleration time (refer to specifications of braking resistor)   
P1/ P 
DC reactor connecting terminals   
For  
220V:0.5~10HP,  
440V:1~15HP 
B1/P 
B2 
- 
Ө 
z  B1/P- Ө: DC power supply input 
B1/P-B2: External braking resistor
For 220V: 15~20HP and 440V: 20HP
♁ 
- 
z  ♁- Ө : DC power supply input or 
External braking unit.   
For 220V: 25~40HP and 440V: 25~75HP
U / T1   
V / T2   
W / T3 
Inverter outputs 
y Do not remove the P-P1 jumper if there is no DC reactor connected.   
 
Descriptions of 
CVP control circuit terminals 
Symbol  Description 
R2A 
R2B 
Multifunctional terminal – Normal open 
R1C 
 Common contact 
R1B 
  Normal close contact 
R1A 
  Normal open contact 
Multifunctional output 
terminals 
Contact rated capacity: 
(250VAC/1A or 30VDC/1A) 
 
10V  Frequency knob (VR) power source terminal (pin 3) 
AIN 
  Analog frequency signal input terminal or multifunction input terminals S7 (H level:>8V, L 
level:<2V, PNP only) 
24V 
Common contact for S1~S5 (S6, S7) in PNP (Source) input. Shift to PNP position (refer to 
wiring diagram) of SW1 when used PNP input 
COM 
24G 
AGND 
1. Common contact and analog input /output signal for S1~S5 in NPN (Sink) input.     
    Shift to NPN position (refer to wiring diagram I) of SW1 when used NPN input.   
2. AGND for AIN, 
I2 and FM+ (analog input /output signal) & 24G for S1~S6 (digital input 
/output signal in NPN (Sink) input). Shift to NPN position (refer to wiring diagram II) of SW1 
when used NPN input. 
FM+ 
The positive analog output for multifunction, the signal for output terminal is 0-10VDC (below 
2mA). 
S1 
S2 
S3 
S4 
S5 
Multifunctional input terminals 
S6 
1. Multifunction input terminals (Digital terminal H level:>8V, L level:<2V, PNP only) or analog 
input terminal AI2(0~10Vdc/4~20mA) 
2. The V2.9 version (contains) above the edition, S6 only is the Multi-function input terminal 
use, AI2 have replaced S6 to take analog input use. (Above wiring diagram refers for 
2.2~30KW at 220V and 2.2~55KW at 440V only.)