7 
3.2 Fuse types: 
Drive input fuses are required to disconnect the drive from power in the event of a component failure in 
the drive’s power circuitry. The drive’s electronic protection circuitry is designed to clear drive output 
short circuits and ground faults without blowing the drive input fuses. Table below shows the 
recommended input fuse ratings for CVP inverter. For effective protection use fuses with current-limit 
function, non delay type, also consider the applicable national and international regulations for short 
circuit and over current protection. 
For UL type approval consider the following fuse types RK5, CC or T. 
For non UL type approval consider gG and aR type fuses. 
gG:-    (Overload and Short circuit protection) 
aR ultra rapid    (Short circuit protection only), suitable for protection of Power semiconductors. 
TECO Molded case circuit breakers can be used in Place of the input fuse, consider the necessity 
of back up fuse to provide correct protection according to the applicable national and   
international regulations. Consult with your fuse suppliers if in doubt. 
 JNTHBCBA- HP KW KVA
100% CONT 
Output AMPS (A)
Max.RK5 
FUSE  Rating(A) 
Max.CC or T 
FUSE  Rating(A)
R500AC 0.5 0.4 1.2 3.1  10  20 
0001AC 1 0.75 1.7 4.5  15  30 
0002AC 2 1.5 2.9 7.5  20  40 
 
220V class(1φ) 
0003AC 3 2.2 4.0 10.5  25  50 
R500BC 0.5 0.4 1.2 3.1  8  10 
0001BC 1 0.75 1.7 4.5  12  15 
0002BC 2 1.5 2.9 7.5  15  20 
0003BC 3 2.2 4.0 10.5  20  30 
0005BC 5 3.7 6.7 17.5  30  50 
7R50BC 7.5 5.5 9.9 26  50  60 
0010BC 10 7.5 13.3 35  60  70 
0015BC 15 11.0 20.6 48  80  100 
0020BC 20 15.0 27.4 64  100  125 
0025BC 25 18.5 34.0 80  125  150 
0030BC 30 22.0 41.0 96  160  200 
220V class(3φ) 
 
0040BC 40 30.0 54.0 130  200  250 
0001BE 1 0.75 1.7 2.3  6  10 
0002BE 2 1.5 2.9 3.8  10  15 
0003BE 3 2.2 4.0 5.2  10  20 
0005BE 5 3.7 6.7 8.8  20  30 
7R50BE 7.5 5.5 9.9 13  25  35 
0010BE 10 7.5 13.3 17.5  30  50 
0015BE 15 11.0 20.6 25  50  60 
0020BE 20 15.0 27.4 32  60  70 
0025BE 25 18.5 34.0 40  70  80 
0030BE 30 22.0 41.0 48  80  100 
0040BE 40 30.0 54.0 64  100  125 
0050BE 50 37.0 68.0 80  125  150 
0060BE 60 45.0 82.0 96  150  200 
440V class(3φ) 
 
 
0075BE 75 55.0 110.0 128  200  250 
*Fuse ratings are based upon 300V fuses for 230V inverter, and 500V for 460V inverters