Chapter 3    Notice for wiring 
3.1 Precautions for Peripheral Applications 
 
 
Power supply: 
z  Make sure the voltage applied is correct to 
avoid damaging the inverter. 
z  A molded-case circuit breaker must be 
installed between the AC source and the 
inverter 
Molded-case circuit breaker:   
z  Use a molded-case circuit breaker that 
conforms to the rated voltage and current of 
the inverter to control the power ON/OFF and 
protect the inverter. 
z  Do not use the inverter as the switch for 
run/stop switch. 
Leakage breaker:   
z  Install a leakage breaker to prevent error 
operation caused by electric leakage and to 
protect operators 
z  Setting current should be 200mA or above and 
the operating time at 0.1 second or longer to 
prevent malfunction. 
Magnetic contactor:   
z  Normal operations do not need a magnetic 
contactor. But a contactor has to be installed in 
primary side when performing functions such 
as external control and auto restart after power 
failure, or when using brake controller.   
z  Do not use the magnetic contactor as the 
run/stop switch of the inverter. 
AC reactor for power improvement: 
z  When inverters below 200V/400V 15KW are 
supplied with high capacity (above 600KVA) 
power source or an AC reactor can be 
connected to improve the power performance.
Install fast action fuse (If necessary): 
z  To ensure the safety of peripheral devices, 
please install the fast action fuse. Regarding 
the specification, please refer to P7. 
Input noise filter:   
z  A filter must be installed when there are 
inductive load around the inverter 
Inverter:  
z  Input power terminals L1, L2, and L3 can be 
used in any sequence regardless of phases. 
z  Output terminals T1, T2, and T3 are connected 
to U, V, and W terminals of the motor. If the 
motor is reversed while the inverter is forward, 
just swap any two terminals of T1, T2, and T3.
z  To avoid damaging the inverter, do not connect 
the input terminals T1, T2, and T3 to AC 
power. 
z  Connect the ground terminal properly. 200 V 
series: class 3 grounding, <100Ω; 400 V 
series : <10Ω. 
 
 
 
Power 
Molded-case 
circuit breaker 
Magnetic 
contactor 
C reactor for 
power 
improvement 
Install fast 
action fuse 
(If necessary) 
Input noise 
filter 
CVP inverter 
 
Ground 
Three-phase 
cage motor 
Ground