Target pressure still limit by 18-1(Max. pressure limit), 18-2(Min. pressure
limit).
Control of multifunction analog output
(32)20-A Multifunction analog output selection:
0: Output Frequency
1: Frequency command
2: Output voltage
3: DC voltage
4: Output circuit
5: PID feedback signal
20-B Gain control of multifunction analog output = 0~200%
Multifunction analog output terminal (TM2) is a 0~10Vdc analog output, it is
selectable as 20-A, and when external voltage meter or peripheral equipment has
an error, 20-B is use for adjust it.