Chapter 6 FBD Block  Diagram Programming    142 
IO Link function block 
Up to 8 additional SG2 units can be configured as independent Slave nodes, each running their own logic program and 
their I/O linked to one Master smart relay. The Master smart relay’s ID must be 00, and Slave nodes’ ID should 
start with 01 and be continuous. If nodes’ ID isn’t continuous, the Master won’t communication with those 
nodes which are behind the first broken. For example, the nodes’ ID is 01, 02, 04 and 05. The Master thinks 
there are only two Slave nodes whose ID is 01 and 02, and communication with them.   
Each controller can use 8 IO Link (L01~L08). Only one IO Link instruction can work at Mode 1(send mode), 
and the other IO Link instructions must be Mode 2 (receive mode). 
The Mode 1: Send memory range is determined by the Controller ID. The adjacent table show the memory range of 
Wxx locations associated with each controller ID. 
The Mode 2: read the selected Wxx status and write to the selected coil. If the select coil type is input coil I or X, coil 
status can’t be changed by Wxx status. 
 
 
 
FBD output coil display 
M01: enable input coil 
Press “OK” button into 
function display 
Press “SEL” , “↑ ↓” and “OK” 
to modify mode, coil number, 
coil type and W address 
 
 
 
 
Display Description    Type of points  Range 
L01: I/O link output terminal (L01~L08)    Inputs  I01~I0C/i01~i0C 
M01: Enable Input (I01~ B260)    Outputs  Q01~Q08/q01~q08 
Mode: Setting mode(1,2) 1:sending; 2:receiving    Auxiliary coil  M01~M3F/m01~m3F 
Num: Number of send/receive points (1~8)    Auxiliary coil  N01~N3F/n01~n3F 
I03…I07: Type of send/receive points    Expansion inputs  X01~X0C/x01~x0C 
W09…W13: Send/Receive W Table list location    Expansion outputs Y01~Y0C/y01~y0C 
 
ID Memory list 
location 
0 W01~W08 
1 W09~W16 
2 W17~W24 
3 W25~W32 
4 W33~W40 
5 W41~W48 
6 W49~W56 
7 W57~W64 