Chapter 9 Expansion Module    235 
Baud rate adapt oneself and address set 
 
After PBUS mode powers up, it can identify the baud rate on Profibus automatically when at least one master 
sends right message. The baud rate range is: 9.6Kbit/s ~6Mbit/s. In equipment network, each slave node has a 
difference ID, and the maximal number of ID is 127 (0~126). Its ID can be set by 8-bit switch integration on itself. 
 
SW-1  SW-2  SW-3  SW-4  SW-5  SW-6  SW_7  SW_8  ID 
OFF OFF OFF  OFF OFF OFF OFF *  0 
ON OFF OFF OFF OFF OFF OFF *  1 
OFF ON  OFF  OFF OFF OFF OFF *  2 
ON ON OFF OFF OFF OFF OFF *  3 
OFF OFF ON  OFF OFF OFF OFF *  4 
┈  ┈  ┈  ┈  ┈  ┈  ┈ 
* 
┈ 
ON OFF ON  ON ON ON ON *  125 
OFF ON  ON  ON  ON ON  ON  *  126 
※  The SW_8 bit is reserved. 
 
LED state display 
 
PBUS module has two number of double color LED (green and red) used for fast diagnostics, to indicate the state 
of COMM. Bus and itself. 
 
1)  power LED 
 
State of LED  Description 
Green ON  natural 
Yellow (red and green) flash (4Hz) Hardware error 
Yellow (red and green) flash (2Hz) IO number error 
Red flash (2Hz)  Connection with SG2 error 
Red flash (1Hz)  Read/write order COMM. With Network bus error 
OFF Power down 
 
2)  BUS LED 
 
State of LED  Description 
Green ON  Connect with DP Net and communication right 
OFF  Not connect with DP Net 
 
※  More information about protocol and GSD file to see: 
R09-SG2-DP-C04 X 30(SG2-PROFIBUS-DP manual E) 