Installation & Operation Manual
© 2016 284_D - 05/16
1 of 60
A Watts Water Technologies Company
Multi-Staging
A Flexible Solution for Commercial & Multi-Residential Heating Plants
The Boiler Control 284 is designed to operate up to four
boilers to accurately maintain a target water temperature.
The 284 operates both condensing & non-condensing boilers
that are either modulating, single stage or two stage to
provide a flexible, cost effective mixed boiler plant solution
with better system performance.
The target water temperature is based on outdoor temperature
reset or a fixed setpoint for space or process heating
applications. Additional loads supplied by the 284 include
domestic hot water & fixed setpoint heating. Boiler equal
run-time rotation, stand-by primary pump operation & pump
exercising all increase boiler plant reliability.
The 284 communicates with a Building Automation System
(BAS) using BACnet
®
IP or Modbus
®
for remote monitoring
& adjustment capability. tekmarNet
®
Thermostats or a tN4
Gateway 483 can be added to optimize system performance
& provide remote monitoring capability.
BACnet is a registered trademark of ASHRAE.
ASHRAE does not endorse, approve or test products
for compliance with ASHRAE standards. Compliance of
listed products to the requirements of ASHRAE Standard
135 is the responsibility of BACnet International (BI).
BTL is a registered trademark of BI.
Features
Outdoor temperature reset
Programmable schedules
tekmarNet
®
compatible
Control up to four boilers
Condensing & non-condensing boiler groups
Modulating, single stage or two stage
Boiler isolation valves
BACnet
®
IP or Modbus
®
communication
Primary pump sequencing
DHW priority
Setpoint operation
Combustion air damper control
Energy, flow & pressure monitoring
Benefits
Reduce energy costs
Prolong equipment life
Provide boiler redundancy
Provide primary pump redundancy
Remote monitoring & adjustment options
Combine mid & high efficiency boilers to lower
component cost

Other manuals for Tekmar 284

Questions and Answers

  • J
    James LawrenceSep 7, 2025
    What to do if my Tekmar 284 Controller displays COMBUSTION AIR PROOF FAILURE?
    • T
      thorntonpatrickSep 7, 2025
      If your Tekmar Controller displays a 'COMBUSTION AIR PROOF FAILURE', you should check the CA proving device and its wiring.
  • W
    William BriggsAug 22, 2025
    How to fix CONTROL SETUP FAILURE on my Tekmar 284?
    • M
      Mrs. Michele BarnesAug 22, 2025
      To resolve a 'CONTROL SETUP FAILURE' on your Tekmar Controller, try resetting the defaults and verifying all settings.
  • A
    Angela MartinSep 4, 2025
    What to do if my Tekmar 284 Controller displays PRIMARY PUMP P1 & P2 FLOW PROOF FAILURE?
    • J
      Jennifer WashingtonSep 5, 2025
      If your Tekmar Controller displays 'PRIMARY PUMP P1 & P2 FLOW PROOF FAILURE', you should check the flow proving device and its wiring.
  • C
    conwaysharonSep 3, 2025
    What to do if my Tekmar 284 Controller displays PRIMARY PUMP P2 FLOW PROOF FAILURE?
    • P
      Pamela SalazarSep 3, 2025
      If your Tekmar Controller displays 'PRIMARY PUMP P2 FLOW PROOF FAILURE', you should check the flow proving device and its wiring.
  • E
    Edward HooverSep 2, 2025
    What to do if my Tekmar 284 displays PRIMARY PUMP P1 FLOW PROOF FAILURE?
    • P
      Paul RiggsSep 2, 2025
      If your Tekmar Controller displays 'PRIMARY PUMP P1 FLOW PROOF FAILURE', you should check the flow proving device and its wiring.
  • S
    Scott FosterAug 31, 2025
    What to do if my Tekmar 284 Controller shows a BOILER (#) OUTLET SENSOR ERROR?
    • C
      Cory ChristianSep 1, 2025
      If your Tekmar Controller displays a 'BOILER (#) OUTLET SENSOR ERROR', it means the control failed to read the boiler (#) outlet sensor due to an open or short circuit. Check the boiler (#) outlet sensor and its wiring.
  • V
    Veronica FullerAug 30, 2025
    What to do if my Tekmar 284 is showing VENT SENSOR ERROR?
    • N
      nathan44Aug 30, 2025
      If your Tekmar Controller is showing a 'VENT SENSOR ERROR', this indicates the control couldn't read the vent sensor due to an open or short circuit. Try checking the vent sensor and its wiring.
  • B
    Brianna BartonAug 29, 2025
    What to do if my Tekmar 284 Controller shows a BOILER INLET SENSOR ERROR?
    • B
      Blake Tran MDAug 29, 2025
      If your Tekmar Controller displays a 'BOILER INLET SENSOR ERROR', it means that the control failed to read the boiler inlet sensor due to an open or short circuit. You should check the boiler inlet sensor and its wiring.
  • A
    Andrea GarzaAug 27, 2025
    What to do if my Tekmar Controller shows an OUTDOOR SENSOR ERROR?
    • S
      stevenallenAug 27, 2025
      If your Tekmar Controller displays an 'OUTDOOR SENSOR ERROR', the control was unable to read the outdoor sensor due to an open or short circuit. You should check the outdoor sensor and its wiring.
  • A
    Ashley HunterAug 27, 2025
    What to do if my Tekmar 284 displays a DHW SENSOR ERROR?
    • I
      Isabella TerryAug 27, 2025
      If your Tekmar Controller displays a 'DHW SENSOR ERROR', it means the control couldn't read the DHW sensor because of an open or short circuit. To fix this, check the DHW sensor and its wiring.

Summary

Sequence of Operation

Boiler (Source (#) Menu) Setup & Operation

Configures individual boiler settings for optimal plant flexibility.

System Setup & Operation

Application Mode

Selects the primary operating mode for the heating system.

Boiler Minimum

Sets the lowest allowable target temperature for the boiler.

Outdoor Temperature Reset Operation

Characterized Heating Curve

Determines target water temperature based on outdoor air temperature.

Setpoint Operation

Setpoint Mode

Enables or disables setpoint heating operation for various loads.

Indirect Domestic Hot Water (IDHW) Operation

DHW Call

Describes methods to request indirect domestic hot water.

Building Automation System (BAS)

BAS Type

Selects between Modbus® and BACnet® IP communication protocols.

Pump Operation

Primary Pump Operation

Explains primary pump sequencing, stand-by operation, and logging.

Flow Proof Call

Proves flow after pump activation to ensure proper operation.

Control Wiring

Wiring the Input Power

Details how to connect the 115V AC input power to the control.

Wiring the Boiler Pumps; Valves

Explains wiring for boiler pumps and isolation valves.

Sensor Installation & Wiring

Mounting the Outdoor Sensor

Guides on mounting the outdoor sensor for accurate temperature readings.

Wiring the Outdoor Sensor (tekmar 070)

Wiring Boiler Outlet Sensors (tekmar 082)

Explains how to wire boiler outlet sensors for temperature monitoring.

EMS, Modbus & BACnet Connections

EMS Connection

Describes how to connect an Energy Management System to the control.

Testing the Control Wiring

User Test (HAND)

Explains how to use the HAND mode for manual operation and testing.

Control Settings

Access Level

Manages access levels for different users to menus and settings.

DIP Switch Settings

Configures key features like flow proof and schedule operation via DIP switches.

User Interface

Display

Describes the different fields and components of the control's display.

Setup Menu (1 of 6)

APP MODE

Selects the main operating mode: RSET, SETP, DDHW, EMS, or BAS.

BOILER MINIMUM

Defines the minimum allowed boiler target temperature for non-condensing groups.

Source # Menu (1 of 2)

BOILER ENABLE

Selects whether a specific boiler is operational or disabled.

BOILER TYPE

Selects boiler operation type: modulating, single-stage, two-stage, or EMS.

Monitor # Menu (1 of 1)

BURNER RUN TIME

Records the total running time of the boiler since the last clear.

Monitor Menu (1 of 2)

PRIMARY PUMP 1 RUN TIME

Records the total running time of primary pump 1 since last cleared.

Troubleshooting

Error Messages (1 of 3)

Lists common error messages and their potential causes and solutions.

Error Messages (2 of 3)

Lists additional error messages and troubleshooting tips.

Error Messages (3 of 3)

Lists remaining error messages and troubleshooting guidance.

Technical Data

Limited Warranty & Product Return Procedure

Outlines the terms and conditions of the product warranty and return process.

Tekmar 284 Specifications

General IconGeneral
CategoryController
ApplicationHydronic heating systems
Zones SupportedUp to 4
Power Supply24 VAC
OutputRelay
MountingWall mount
Control MethodOn/Off
DisplayLED
Input Voltage24 VAC
Output Voltage24 VAC

Related product manuals