EasyManua.ls Logo

Temp-Cast 2000 - Heat Control and Efficiency

Default Icon
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 2 – Chimneys & Dampers
Temp-Cast 2000 Installation Manual February 2010
7
Fig 3
A 4” grinder with a diamond blade is ideal for
cutting accurate & neat holes in the refractory
concrete modules.
FACTORY-BUILT CHIMNEYS
We do not recommend exterior chimneys, (see
Sec. 4 of the Temp-Cast Planning Guide) but if a
chimney on the outside of the house is
unavoidable, then an insulated factory-built (e.g.
"HT" or 2100F.) chimney is the better choice.
When a factory-built chimney is started at the
floor level, there will not be sufficient space to
access the clean-out cap under it. In order to
provide a clean out access, one of the following
2 methods is suggested.
Create a masonry connection to the fireplace,
with 8" (200mm) round flue tile. Add vertical
sections of 8” round flue tile, with a clean-out
access built into the first vertical section. Wrap
the horizontal tile and the first vertical flue tile
with “ceramic wool” blanket & ensure they
cannot be dislodged. Continue with flue tile &
masonry to the point where the transition to
factor-built chimney is wanted – often the
masonry is extended to the first ceiling. If a
roof-top damper is to be installed, the cable
protector for the damper cable must be built into
the masonry chimney where it will be accessible
for daily use – we recommend at least 6 feet
from the floor. Install an anchor plate approved
for the factory-built chimney, on top of the last
masonry section - the factory-built chimney
continues from this point. (See Fig. 5.) If the
factory-built chimney will also be enclosed in
masonry, the layout of the first masonry courses
must take this into account. (Confirm this
connection method with your local building
official.)
Fig 4

Other manuals for Temp-Cast 2000