The default heat pump size setting at shipping is NO SIZE (indicated
by an asterisk next to the English text). This means that the compres-
sor cannot start and the installer must first select language and a then
heat pump size before leaving this menu. After the size has been set a
factory reset starts. The installation will be set for radiator heating after
the factory reset. For floor heating do a new factory reset. See chapter
"Factory setting"
When power is supplied to the control unit, the first menu that appears in the display is the DIRECT EVAP. Menu. A heat pump size must
be set before configuring the control system and completing the commissioning.
To set the heat pump size initially:
▪
Use or buttons to select machine profile.
▪
Press to confirm the choice. An asterisk (*) will appear next to the chosen profile and press to continue.
▪
Use
or buttons to select outdoor unit size.
▪
Press to confirm the choice. An asterisk (*) will appear next to the chosen size and press to continue.
▪
After selecting the size, the factory setting is set and "WAIT..." is displayed in the meantime.
It is possible to select the heat pump size at a later stage by changing
the settings in the Service Menu as described below.
To enter the Service Menu, press and hold for at least 5 seconds. Use or buttons to move up and down in the menu.
Set the output size of the heat pump in the menu:
▪
SERVICE
▪
INSTALLATION
▪
SYSTEM
▪
HEAT SOURCE
▪
AIR
▪
DIRECT EVAP.
▪
Press
for approximately 10 seconds to enter the Heat Pump machine profile and size entry.
▪
Use or buttons to select machine profile.
▪
Press to confirm the choice. An asterisk (*) will appear next to the chosen profile and
press to continue.
▪
Use or to select outdoor unit size.
▪
Press to confirm the choice. An asterisk (*) will appear next to the chosen size
and press
to continue.
▪
After selecting the size, the factory setting is set and "WAIT..." is displayed in
the meantime.
Commissioning