Setup
Menu Defaults
The tables below detail the default values and the range of available settings, plus any additional information about the
unit's congurable settings.
SETUP1
Congurable Item Range Default Additional information
Min Max
Time Any Time 00:00 24 hour clock.
Day of Week 1 7 1 Two groups, ve week days & two
weekend days.
Backlight Brightness O 4 1 O, 25%, 50%, 75% & 100%
Boost Overrun Kitchen 0 mins 60 mins 15 mins
Wet Room 0 mins 60 mins 15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the aurastat's fan button to trigger boost.
The aurastat's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer 0 mins 60 mins 0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the aurastat's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Boost Inhibit On/O On O O
Boost Inhibit Times Start 00:00 23:59 23:00
End 00:00 23:59 05:00
Internal Humidity Boost
(Setpoint)
30% 89% 70%
SETUP2
Congurable Item Range Default Additional information
Min Max
Filter Change Interval 3 months 24 months 12 months
Boost Overrun Timer Kitchen 0 mins 60 mins 15 mins
Wet Room 0 mins 60 mins 15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the aurastat's fan button to trigger boost.
The aurastat's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer 0 mins 60 mins 0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the aurastat's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Speed 4 SUMMERboost® 14% 100% 100% SUMMERboost® is only available on
models with Summer. SUMMERboost®
is disabled by default.
Press and release the + / - key to modify the mantissa(decimal). Press and hold the + / - key to modify the characteristic
(interger). HRV fan speed will change to reect the displayed setting when the button is released. Changes in fan speed
will take time to be reected as changes to the ventilation system airow rates. Fan speed will not change while in this
conguration menu.
Boost Alert On/O On O On
Boost Alert Timer 1 hour 10 hours 2 hours