Congurable Item Range Default Additional information
Min Max
Room Sensor 2 Enable/
Disable
Enable Disable Disable Activates Setup Room Sensor 1 in SETUP2
menu.
Room Sensor Type CO₂ Options are;
Temperature Sensor - °C,
CO₂ Sensor - PPM,
Air Quality Sensor - PPM,
Humidity Sensor - %RH.
Settings required for Titon supplied
sensors:
Sensor
Type
Titon
Part №
Min
0V
Max
10V
°C TP543 0000 0040
CO₂ PPM TP541 0450 1850
AQ PPM TP540 0450 1850
%RH TP542 0020 0090
Consult manufactures data sheets for
details.
Sensor Min Point 0V 0 9999 450PPM
Sensor Max Point 10V 0 9999 1850PPM
0000 9999
Continuous SPEED 2
Proportional Increase
450
Sensor
Min Point
0V
1850
Sensor
Max Point
10V
800
Set Point
Low
1400
Set Point
High
Boost SPEED 3
Switch Input 1 Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room,
Setback,
Summer Mode Engage / SUMMERboost®
Disable.
Switch Input 2 Boost from Wet
Room
Switch Input 3 Summer Mode
Engage /
SUMMERboost®
Disable.
Live Switch 1 (LS1) Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room.
Live Switch 2 (LS2) Boost from Wet
Room
RESET4
Congurable Item Range Default Additional information
Min Max
Passcode 6840
Reset Yes No No Selecting Yes returns ALL conguable
values except commissioned fan speeds
to the preceding default values and
returns to SETUP1 menu.
20