Congurable Item Range Default Additional information
Min Max
Room Sensor 2 Enable/
Disable
Enable Disable Disable Activates Setup Room Sensor 1 in SETUP2
menu.
Room Sensor Type CO₂ Options are;
Temperature Sensor - °C,
CO₂ Sensor - PPM,
Air Quality Sensor - PPM,
Humidity Sensor - %RH.
Settings required for Titon supplied
sensors:
Sensor
Type
Titon
Part №
Min
0V
Max
10V
°C TP543 0000 0040
CO₂ PPM TP541 0450 1850
AQ PPM TP540 0450 1850
%RH TP542 0020 0090
Consult manufactures data sheets for
details.
Sensor Min Point 0V 0 9999 450PPM
Sensor Max Point 10V 0 9999 1850PPM
0000 9999
Continuous SPEED 2
Proportional Increase
450
Sensor
Min Point
0V
1850
Sensor
Max Point
10V
800
Set Point
Low
1400
Set Point
High
Boost SPEED 3
Switch Input 1 Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room,
Setback,
Summer Mode Engage / SUMMERboost®
Disable.
Switch Input 2 Boost from Wet
Room
Switch Input 3 Summer Mode
Engage /
SUMMERboost®
Disable.
Live Switch 1 (LS1) Boost from
Kitchen
Options are;
Boost from Kitchen,
Boost from Wet Room.
Live Switch 2 (LS2) Boost from Wet
Room
RESET4
Congurable Item Range Default Additional information
Min Max
Passcode 6840
Reset Yes No No Selecting Yes returns ALL conguable
values except commissioned fan speeds
to the preceding default values and
returns to SETUP1 menu.
20