Titon TP534 - Installed Configuration; Setup1; Setup2; Setup3

Titon TP534
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SETUP1
Congurable Item Setting
Backlight Brightness One
Boost Overrun Kitchen 15 mins
Wet Room 15 mins
Boost Delay Timer Kitchen 0 mins
Wet Room 0 mins
Boost Inhibit On/O O
Boost Inhibit Times Start 23 : 00
End 05 : 00
%RH Boost Set point 70 %
SETUP2
Congurable Item Default
Filter Change Interval 12 months
Boost Overrun Timer Kitchen 15 mins
Wet Room 15 mins
Boost Delay Timer 0 mins
Speed 4 SUMMERboost® Supply 100 %
Extract 100 %
Boost Alert On/O On
Boost Alert Timer 2 hours
Summer Mode Enable/
Disable
Disable
Summer Mode Extract 22 °C
Supply 18 °C
Supply Fan
Speed
0 %
Summer By Pass Enable/
Disable
Enable
Summer By Pass Extract 25 °C
Supply 18 °C
SUMMERboost® Enable
Duct Heater Enable/
Disable
Disable
Duct Heater Frost
Hyst 1 °C
Duct Heater threshold 4 °C
Congurable Item Default
Room Sensor 1
Set point Low 0060
Set point High 0070
Room Sensor 2
Set point Low 0800
Set point High 1400
Internal Humidity Boost O
%RH Boost Overrun
timer
15 %
%RH Boost Hysterisis 1 %
SETUP3
Congurable Item Default
Continuous SPEED2 Supply 40 %
Extract 40 %
Boost SPEED3 Supply 70 %
Extract 70 %
Setback SPEED1 Supply 18 %
Extract 18 %
SPEED4 SUMMERboost® Supply 100 %
Extract 100 %
Frost set point 2 °C
Frost Protection Mode O
Room Sensor 1 Enable/
Disable
Disable
Room Sensor Type %RH
Sensor Min Point 0V 0020
Sensor Max Point 10V 0090
Room Sensor 2 Enable/
Disable
Disable
Room Sensor Type CO₂
Sensor Min Point 0V 0450
Sensor Max Ponit 10V 1850
Switch Input 1 Kitchen
Switch Input 2 Wet Room
Switch Input 3 SUMMERboost®
Live Switch 1 (LS1) Kitchen
Live Switch 2 (LS2) Wet Room
Installed Conguration.
The Tables below MUST be completed by the installer with all congured setting that deviate from the defaults.
Default values shown greyed out.
22