SETUP1
Congurable Item Setting
Backlight Brightness One
Boost Overrun Kitchen 15 mins
Wet Room 15 mins
Boost Delay Timer Kitchen 0 mins
Wet Room 0 mins
Boost Inhibit On/O O
Boost Inhibit Times Start 23 : 00
End 05 : 00
%RH Boost Set point 70 %
SETUP2
Congurable Item Default
Filter Change Interval 12 months
Boost Overrun Timer Kitchen 15 mins
Wet Room 15 mins
Boost Delay Timer 0 mins
Speed 4 SUMMERboost® Supply 100 %
Extract 100 %
Boost Alert On/O On
Boost Alert Timer 2 hours
Summer Mode Enable/
Disable
Disable
Summer Mode Extract 22 °C
Supply 18 °C
Supply Fan
Speed
0 %
Summer By Pass Enable/
Disable
Enable
Summer By Pass Extract 25 °C
Supply 18 °C
SUMMERboost® Enable
Duct Heater Enable/
Disable
Disable
Duct Heater Frost
Hyst 1 °C
Duct Heater threshold 4 °C
Congurable Item Default
Room Sensor 1
Set point Low 0060
Set point High 0070
Room Sensor 2
Set point Low 0800
Set point High 1400
Internal Humidity Boost O
%RH Boost Overrun
timer
15 %
%RH Boost Hysterisis 1 %
SETUP3
Congurable Item Default
Continuous SPEED2 Supply 40 %
Extract 40 %
Boost SPEED3 Supply 70 %
Extract 70 %
Setback SPEED1 Supply 18 %
Extract 18 %
SPEED4 SUMMERboost® Supply 100 %
Extract 100 %
Frost set point 2 °C
Frost Protection Mode O
Room Sensor 1 Enable/
Disable
Disable
Room Sensor Type %RH
Sensor Min Point 0V 0020
Sensor Max Point 10V 0090
Room Sensor 2 Enable/
Disable
Disable
Room Sensor Type CO₂
Sensor Min Point 0V 0450
Sensor Max Ponit 10V 1850
Switch Input 1 Kitchen
Switch Input 2 Wet Room
Switch Input 3 SUMMERboost®
Live Switch 1 (LS1) Kitchen
Live Switch 2 (LS2) Wet Room
Installed Conguration.
The Tables below MUST be completed by the installer with all congured setting that deviate from the defaults.
Default values shown greyed out.
22