198 ACE-tronics G9 ASD Installation and Operation Manual
RS485 2-Wire and 4-Wire Communications Time-Out Action
Program Communications Communication
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
No Action/No Action
Alarm/No Action
Trip/No Action
No Action/Alarm
Alarm/Alarm
Trip/Alarm
No Action/Trip
Alarm/Trip
Trip/Trip
Direct Access Number F804
Parameter Type — Selection List
Factory Default Trip/Trip
Changeable During RunYes
RS485 2-Wire Send Wait Time
Program Communications Communication
This parameter sets the RS485 2-Wire response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number F805
Parameter Type — Numerical
Factory Default 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F804 F805