ACE-tronics G9 ASD Installation and Operation Manual 197
RS485 2-Wire Baud Rate
Program Communications Communication
This parameter plays a role in the setup of the communications network by
establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
9600
19200
38400
Direct Access Number F800
Parameter Type — Selection List
Factory Default 19200
Changeable During RunYes
Units — bps
RS485 2-Wire and 4-Wire Parity
Program Communications Communication
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
No Parity
Even Parity
Odd Parity
Direct Access Number F801
Parameter Type — Selection List
Factory Default Even Parity
Changeable During RunYes
ASD Number
Program Communications Communication
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number F802
Parameter Type — Numerical
Factory Default 0
Changeable During RunYes
Minimum — 0
Maximum — 247
RS485 2-Wire and 4-Wire Communications Time Out
Program Communications Communication
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number F803
Parameter Type — Numerical
Factory Default 0 (Off)
Changeable During RunYes
Minimum — 0 (Off)
Maximum — 100
Units — Seconds