88 H7 ASD Operation Manual
RR Speed Reference Setpoint #1 (%)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
RR
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
Perform the following setup to allow the system to receive control input at the
RR terminal:
•Program
Fundamental Parameters
Standard Mode Selection
Command Mode
Use Control Terminal Strip.
•Program
Fundamental Parameters
Standard Mode Selection
Frequency Mode #1
Use RR.
Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine the gain
and bias of the RR terminal are:
RR Speed Reference Setpoint #1 (frequency) (F211),
•the RR input signal level that represents RR Speed Reference Setpoint #1
(frequency): F210,
RR Speed Reference Setpoint #2 (frequency) (F213), and
•the RR input signal level that represents RR Speed Reference Setpoint #2
(frequency): F212.
When operating in the Torque Control mode, the settings that determine the
gain and bias of the RR terminal are:
Torque Reference Setpoint #1 (%) (F214),
•the RR input signal level that represents the RR Torque Reference
Setpoint #1 (%): F210,
Torque Reference Setpoint #2 (%) (F215), and
•the RR input signal level that represents the RR Torque Reference
Setpoint #2 (%): F212.
Once set, as the RR input voltage changes, the output frequency or the output
torque of the drive will vary in accordance with the above settings.
This parameter sets the RR input level that represents RR Speed Reference
Setpoint #1 (torque or frequency). This value is entered as 0 – 100% of the
0 – 10 VDC RR input signal range.
The input signal may be trimmed using F472 (Bias) and F473 (Gain).
This parameter sets the RR input level that represents RR Speed Reference
Setpoint #1 (torque or frequency). This value is entered as 0 – 100% of the RR
input signal range.
Direct Access Number F210
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
Frequency Settings
Torque Settings
F210 F210