54
Check code Operation cause
[A0]
Discharge temp. sensor (TD1) short circuit TD1 sensor open/short
Open/short of TD1 sensor was detected. Check connector (TD1 sensor: PJ1) and characteristics of
sensor resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check code Operation cause
[A1]
Discharge temp. sensor (TD2) short circuit TD2 sensor open/short
Open/short of TD2 sensor was detected. Check connector (TD2 sensor: PJ2) and characteristics of
sensor resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check code Operation cause
[A2]
Suction temp. sensor (TS) short circuit TS1 sensor open/short
Open/short of TS1 sensor was detected. Check connector (TS1 sensor: PJ3) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check code Operation cause
[A4]
External air sensor (Tho) short circuit Tho sensor open/short
Open/short of Tho sensor was detected. Check connector (Tho sensor: PJ5) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check code Operation cause
[A5]
Outdoor heat exchange sensor (TE) short circuit TE sensor open/short
Open/short of TE sensor was detected. Check connector (TE sensor: PJ4) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Troubleshooting
Diagnostic procedure for check code