Domestic Hot Water Heat Pump Service Manual
25
7.10.1 PV ECO operation in AUTO mode
When the photovoltaic mode is set to PV ECO and the DHW-HP mode is set to AUTO, there is no
operation of the electrical heater, even if the 0~10V input rises above the D21 (PV Min Voltage EL)
set point.
0~10V input raised in small steps until >5V, set from D20 (PV Min Voltage HP)
HP starts after 5 minutes delay, set from D22 (PV Min Time)
In ECO / AUTO mode the heater should not operate, Voltage raised to >8V D21 (PV Min Voltage
EL)
0~10V input decreased until <5V, set from D20 (PV Min Voltage HP)
HP stops after 5 minutes delay, set from D22 (PV Min Time)
Note: If water set point temperature is achieved then the heat pump stops operation.