DHW-HP normal operation
SB Block – SG switch positions: SG1 ON, SG2 Off – DHW-HP stops operation
SG Boost – SG switch positions; SG1 On, SG2 On – DHW-HP operates with HP & EL Heater
SG Eco – SG Switch positions; SG1 Off, SG2 On – DHW-HP operates with HP only
When DHW-HP reaches mode set point (AUTO mode = 53.5°C), DHW-HP stops operation
7.13 D29 External control
This function allows for the external control of the ventilation function using a 0 ~ 10 Volt input.
Using the installer menu, D29 (External control) function.
The fan always runs according to the input signal in GC1 (0-10V) from an
external hygrostat, CO
2
– sensor or similar appliances.
1. If the voltage is between 0-3.0V the fan speed id D5 (Fan min speed)
2. If the voltage is between 3.0-8.0V the fan speed is D4 (Fan medium
speed)
3. If the voltage is higher than 8V the fan speed is D3 (Fan max speed)
If the ventilation function is already selected,
a signal higher of 2V to GC1 leads to maximum air flow.