– 132 –
4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section
to that you want.
5 Push the button.
6 Push the button (left side of the button) repeatedly to select another indoor UNIT No. to
change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the button (left side of the button) to check the changed addresses.
8 If the addresses have been changed correctly, push the button to finish the procedure.
To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change the addresses.
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line
following step
2.
(Execute it while the units are stopped.)
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display.
2 Push (left side of the button) and buttons repeatedly to select a system address.
UNIT LOUVER
UNIT LOUVER
3
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Cancels the line selection
UNIT LOUVER
SWING/FIX