– 274 –
Indoor Unit
Points to Note When Replacing Indoor P.C. Board Assembly
The electrically erasable programmable read-only memory (hereinafter EEPROM, IC10) mounted on an indoor
P.C. board holds important setting data, including the type and capacity codes intrinsic to the model (set at the
factory), as well as the line/indoor/group addresses, high ceiling adjustment setting and the like (during installation,
either automatically or manually). Proceed with the replacement of an indoor P.C. board assembly in accordance
with the procedure described below.
After completion of the work, check the settings again, including the indoor unit No. and group header/follower
designation, and confirm the integrity of the refrigerating cycle by conducting a test operation, etc.
<Replacement procedure>
Method 1
If it is possible to turn on the indoor unit and read the setting data from the P.C. board to be replaced via a wired
remote controller -
Reading EEPROM data: Procedure 1
Replacing P.C. board and turning on power: Procedure 2
Writing EEPROM data in new EEPROM: Procedure 3
Resetting power supply (applicable to all indoor units connected to remote controller in case of group operation)
epyt ledoMedoc traP P.C. board type
431-6V-379 MMU-AP 0751-CCMseires H2
431-6V-437
MMU-AP
2WH series
MMU-AP
1MH series
MMU-AP
2SH series
MMC-AP
1H series
MMD-AP
1SPH/SH series
MCC-1402
431-6V-325 MMD-AP
2041-CCMseires HB1
431-6V-326
MMU-AP
1WH series
MMU-AP
1YH series
MMD-AP
1H series
MMF-AP
1H series
MML-AP
1H series
MML-AP
1BH series
MCC-1403
431-6V-343 MMD-AP
3041-CCMseires EFH1
1
3
P.C. BOARD EXCHANGE PROCEDURES
13-1. Replacement of Indoor P.C. Boards