18 P9 ASD Quick Start Guide
Terminal Descriptions
Note: The programmable terminal assignments may be accessed and changed from the
default settings as mapped on pg. 40 or via the Direct Access method: Program
Direct Access Applicable Parameter Number. See the section titled Program
Mode Menu Navigation on pg. 40 for the applicable Direct Access parameter
numbers. For further information on terminal assignments and default setting
changes, see the sections titled Terminal on pg. 42 and Default Setting Changes on
pg. 33.
Note: See the section titled Cable/Terminal/Torque Specifications on pg. 90 for the ASD
conductor and terminal electrical specifications.
ST — The default setting for this terminal is the Standby mode controller. As the default setting, this
terminal must be activated for normal system operation. The ST terminal is activated by connecting CC
to this terminal (Sink mode). When deactivated, OFF is flashed on the LED screen and the Not-Ready-
to-Run icon is displayed on the LCD screen as shown in Figure 22 on pg 28. This input terminal may be
programmed to any of the functions listed in the P9 ASD Installation and Operation Manual (See
F113).
RES — The default setting for this terminal is Reset. The RES terminal is activated by connecting CC
to this terminal (Sink mode). A momentary connection to CC resets the ASD and any fault indications
from the display. Reset is effective when faulted only. This input terminal may be programmed to any
of the functions listed in the P9 ASD Installation and Operation Manual (See F114).
F — The default setting for this terminal is the Forward run command. The F terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the P9 ASD Installation and Operation Manual (See F111).
R — The default setting for this terminal is the Reverse run command. The R terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the P9 ASD Installation and Operation Manual (See F112).
S1 — The default setting for this terminal is the Preset Speed 1. The S1 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
fu
n
ctions listed in the P9 ASD Installation and Operation Manual (See F115).
S2 — The default setting for this terminal is the Preset Speed 2. The S2 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the P9 ASD Installation and Operation Manual (See F116).
S3 — The default setting for this terminal is the Preset Speed 3. The S3 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the P9 ASD Installation and Operation Manual (See F117).
S4 — The default setting for this terminal is the Preset Speed 4. The S4 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the P9 ASD Installation and Operation Manual (See F118).
RR — The default function assigned to this terminal is Frequency Mode 1. The RR terminal accepts a
0 – 10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed or torque of the motor via an amplitude setting or regulate by
setting a limit. The gain and bias of this terminal may be adjusted for application-specific suitability
(See F210 – F215).
RX — The default function assigned to this terminal is Torque Command. The RX terminal accepts a
±10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to raise or lower the speed or torque of the motor via an amplitude setting or this