32 P9 ASD Quick Start Guide
Frequency Reference Source (F004)
This selection allows the user to establish the source of the Frequency command.
Settings:
Use VI/II (V/I)
Use RR
Use RX
EOI Keypad
RS485
Communication Option Board
RX2 Option (AI1)
Option V/I
UP/DOWN Frequency
Pulse Input (Option)
Pulse Input (Motor CPU)
Binary/BCD Input (Option)
Display Unit (F701)
This parameter sets the unit of measurement for current and voltage values displayed on the EOI.
Exit >>
This is the final screen of the Standard Startup Wizard. The basic parameters of the ASD have been set. 
Click Exit to return to the Frequency Command Screen. Additional application-specific programming 
may be required.
Operation (Hand)
Note: See the section titled EOI Features on pg. 26 for information on Auto operation.
To turn the motor on, perform the following:
1. Connect the CC terminal to the ST terminal.
2. Press the Mode key until the Frequency 
Command screen is displayed.
3. Press the Hand/Auto key to enter the Hand 
mode (green Hand LED illuminates).
4. Turn the Rotary Encoder clockwise until the 
desired Frequency Command value is 
displayed in the SET field of the LCD screen.
5. Press the Run key and the motor runs at the 
Frequency Command value.
Note: The speed of the motor may be changed while the motor is running by using the Rotary 
Encoder to change the Frequency Command value.
6. Press the Stop-Reset key to stop the motor.