74 P9 ASD Quick Start Guide
Trips/Faults
A Trip is an P9 ASD response to a Fault (though Fault and Trip are sometimes used interchangeably). A
Trip is a safety feature that disables the ASD system in the event that a subsystem of the ASD is
malfunctioning or a parameter setting has been exceeded.
Listed in Table 6 are the Faults that may result in a Trip and the possible causes. When a Trip is incurred
the system displays the Fault screen. The Fault screen identifies the active Fault.
Table 6. P9 ASD Fault Listing.
LED Screen LCD Screen Possible Causes/Troubleshooting
AbFL Low Suction/No Flow
Cut Off
Loss of suction pressure or closed pump output valve.
Activated discrete input terminal set to Low Suction/No Flow Protection.
•ASD Upper-Limit Frequency run-time is equal to F484 time setting.
E Emergency Off Emergency Off command received via EOI or remotely.
E-10 Sink/Source Setting
Error
Improperly positioned Sink/Source jumper on the Terminal board or on an
option device (See J100 at the Terminal PCB of the ASD).
Sink/Source configuration is incorrect.
E-11
Brake Sequence
Response Error
F630 is set to a non-zero value.
Braking sequence discrete input and output terminals are not set up properly.
E-12 Encoder Signal-Loss
Error
ASD is configured to receive a signal from a shaft-mounted encoder and no
signal is being received while running.
Disconnection at the Encoder circuit.
Motor is stopped and is generating torque via torque limit control.
ASD is not configured properly.
E-13 Speed Error Result of a motor speed that is greater than the commanded speed when
using an encoder for speed control.
Improper encoder connection or setup information.
Defective encoder.
E-17
Key Failure Same key input for 20 seconds or more.
E-18
Analog (Terminal)
Input Loss
V/I signal loss.
Terminal Board failure.
P24 over-current condition.
F633 setting is too high.
E-19
CPU Communication
Error
CPU data Transmit/Receive error.
E-20
V/f Control Error Torque processing error.
Make service call.
E-21
CPU Processing Error Software processed incorrectly.
Make service call.
E-22
Logic Input Voltage
Error
Incorrect voltage applied to the discrete input terminals.