P9 ASD Quick Start Guide 73
* Reset ignored if active.
*POFF Control Under-Voltage Under-voltage condition at the 5, 
15, or the 24 VDC supply.
• Defective Control board.
• Excessive load on power supply.
• Low input voltage.
PtSt Reference Point Two speed-reference frequency 
setpoint values are too close to 
each other.
• Two speed reference frequency setpoints are too close to 
each other (increase the difference).
UC Under-Current With the Low-Current Trip 
(F610) parameter enabled, the 
output current of the ASD is 
below the level defined at F611 
and remains there for a time 
longer than the setting of F612.
• Output current too low. 
LED 
Screen
LCD 
Screen
Description Possible Causes/Troubleshooting
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www .ctiautomation.net - Email: info@ctiautomation.net