26 P9 ASD Quick Start Guide
EOI Features
Figure 21. The P9 ASD Electronic Operator Interface Features.
LED Screen
Displays the running frequency, active Fault, or active Alarm information.
Rotary Encoder
— Used to access the P9 ASD menu selections, change the value of a displayed
parameter, and performs the Enter key function. Turn the Rotary Encoder either clockwise or
counterclockwise to perform the Up or Down functions of the displayed menu selection. Press the Rotary
Encoder to perform the Enter (select) function. Press while turning for times-ten increment/decrement.
LCD Screen
— Displays configuration information, performance data (e.g., output frequency, bus
voltage, torque, etc.), diagnostic information, and LED screen information in expanded normal text.
Hand/Auto Key
— Toggles the system to and from the Hand and Auto modes. The Hand/Auto key is
disabled while the Fault screen is active. The Hand/Auto key LED is on when the system is in the Hand
mode. The Hand mode allows the Command and Frequency control functions to be carried out via the
EOI.
The Auto mode enables the Command and Frequency control functions to be carried out via the
Terminal Board, RS485, Communication Board, Pulse Input, or the settings of F003/F004. The (F003/
F004) selection may be made via
Program
Fundamental
Standard Mode Selection
Command
Mode and Frequency Mode 1, respectively.
The availability of Hand mode control (Command and Frequency control) may be disabled via Program
Utilities

Prohibition
Hand/Auto Key Command Override and Hand/Auto Key Frequency
Override. The availability of the Hand mode of operation may be reinstated by changing this setting or
performing a Reset (See F007).
ESC Key
— Returns the system to the previous level of the menu tree, toggles between the EOI
Command screen and the Frequency Command screen, or cancels changes made to a field if pressed
while still in the reverse video mode (dark background/light text). The three functions are menu-specific.
Run Key
— Issues the Run command while in the Hand mode. The Run key LED illuminates green
while stopped or red while running to alert personnel.
Mode Key
— Provides a means to access the three root menus. Pressing the Mode key repeatedly loops
the system through the three root menus (See Figure 26 on pg. 35). While looping through the root menus,
the Program menu will display the root menu screen or the Program sub-menu item being accessed prior
to pressing the Mode key.
LCD Screen
Rotary Encoder
Hand/Auto
Mode
Key
Escape Key
Stop-Reset Key
Key (LED)
Run Key
(LED)
LED Screen
HAND
/AUTO
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www .ctiautomation.net - Email: info@ctiautomation.net