90 P9 ASD Quick Start Guide
Cable/Terminal/Torque Specifications
Installation should conform to the NEC Article 110 (NEC
) (Requirements for Electrical Installations), all 
regulations of the Occupational Safety and Health Administration, and any other applicable national, 
regional, or industry codes and standards.
Note: The following ratings are guidelines and shall not be the sole determining factor of the 
lug or wire size used with the P9 ASD. Application-specific applicables, wire insulation 
type, conductor material, and local and regional regulations are but a few of the 
considerations when selecting the actual lug and wire type to be used with the P9 ASD.
Note: Cable/Terminal specifications are based on the rated current of the P9 ASD and Do Not 
include the 10% Service Factor.
Note: Use only 75° C copper wire/cable for motor and power connections.
For further installation information see the section titled Installation and Connections on pg. 10.
Note: (*) Indicates that the item is one of a set of two parallel cables.
Table 12. 230-Volt P9 ASD Cable/Terminal/Torque Specifications.
Model 
Number
VT130P9U
MCP Rating
(Amps)
Wire/Cable Size Lug Size Range
Terminal 
Board
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for 
Input/Output Power
TB1 – 4 
Terminals
3Ø-Input 3Ø-Output
Recommended Maximum 3Ø-Input 3Ø-Output
In-Lbs./Nm
2010
15
14
10 14 to 8
20
(3-core shield)
Torque to 5.3/0.6
11.5/1.3
2015
2025
2035
30
2055 10
2080
50 8 8 12 to 8 17.7/2.0
2110
2160 75 6
3 8 to 3 21/2.42220 100 4
2270 125 3
2330 150 2 2 12 to 1/0 4 to 1/0 50/5.7 53/6
2400 175 1/0
4/0
6 to 250 2 to 300 275/31 168/19
2500 200 2/0
2600 250 3/0
2750 300 4/0
210K 400 *3/0
6 to 250 275/31
212K 500 *250 *250
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www .ctiautomation.net - Email: info@ctiautomation.net