Loading...
FILE NO. SVM-05026
19
6-2. Operation Data
<Cooling>
<Heating>
Note :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5m
Temperature
condition (°C)
Indoor Outdoor
27/19 35/
Standard
pressure
P (MPa)
1.1
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
13.5 49
Indoor
fan
mode
High
Outdoor
fan
mode
High
Compressor
revolution
(rps)
54
Temperature
condition (°C)
Indoor Outdoor
20/ 7/6
pressure
P (MPa)
2.4
pipe temp.
T1 (°C) T2 (°C)
40 0
Indoor
fan
mode
High
Outdoor
fan
mode
High
Compressor
revolution
(rps)
70