FILE NO. SVM-06027
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-13GKHP-ES2 / RAS-13GAH-ES2
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.70 44.5 High 20/15 7/6
Heating Overload*1 3.12 ~ 3.77 52.0 ~ 56. 8 Low 27/ 24/18
Low temperature 2.20 35.0 High 20/ 10/10
Standard 0.90 10.0 High
27/19
35/24
Cooling Overload 0.99 14.0 High 32/23 43/26
Low temperature 0.65 2.0 Low 21/15 21/15
Standar d
pressure
P
(MPaG)
Surface temp. of heat
exchang er inter changing
pipe
T1
(°C)
Fan speed
(indoor)
50Hz
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Accumulator
Heat exchanger
Propeller fan
Outdoor unit
Capillary tube
1.0x400l
Capillary tube
1.5x1500l
PA150X2C-4FT
Cooling
Heating
Mark( )means check points of Gas Leak.
O.D.:12.7mm O.D.:6.35mm
Cooling
Heating
Packed valve
Packed valve
0.39m
(Connecting pipe)
0.49m
(Connecting pipe)
T1
P
Refrigerant
R410A : 1.08 kg.
(12.7)
(6.35)
12.7
6.35
RAS-13NKHP-AS2 / RAS-13N2AH-AS2