– 23 –
7-2. Operation Data
<Cooling> RAS-M18UAV-E
Temperature
condition (°C)
No. of
operating
units
Operating
combination (unit)
Standard
pressure
Heat exchanger
pipe temp
Indoor
fan
Outdoor
fan
Compresser
revolution
(rps)
Indoor Outdoor A B P (MPa) T1(°C) T2(°C)
27/19 35/–
1 unit
07 1.0 to 1.2 12 to 14 35 to 37 High 700rpm 26
10 0.9 to 1.1 12 to 14 36 to 38 High 700rpm 35
13 0.8 to 1.0 10 to 12 36 to 38 High 850rpm 58
16 0.7 to 0.9 8 to 10 36 to 38 High 850rpm 75
2 units
07 07 0.9 to 1.1 13 to 15 40 to 42 High 850rpm 51
10 07 0.9 to 1.1 13 to 15 40 to 42 High 850rpm 61
10 10 0.9 to 1.1 13 to 15 42 to 44 High 850rpm 71
13 07 0.9 to 1.1 13 to 15 42 to 44 High 850rpm 71
13 10 0.9 to 1.1 13 to 15 42 to 44 High 850rpm 71
16 07 0.9 to 1.1 13 to 15 44 to 46 High 850rpm 71
16 10 0.9 to 1.1 13 to 15 44 to 46 High 850rpm 71
13 13 0.9 to 1.1 13 to 15 44 to 46 High 850rpm 71
16 13 0.9 to 1.1 13 to 15 44 to 46 High 850rpm 71
<Heating> RAS-M18UAV-E
Temperature
condition (°C)
No. of
operating
units
Operating
combination (unit)
Standard
pressure
Heat exchanger
pipe temp
Indoor
fan
Outdoor
fan
Compresser
revolution
(rps)
Indoor Outdoor A B P (MPa) T1(°C) T2(°C)
20/– 7/6
1 unit
07 2.4 to 2.6 37 to 39 2 to 4 High 750rpm 44
10 2.6 to 2.8 45 to 46 2 to 4 High 900rpm 62
13 3.0 to 3.2 51 to 53 2 to 4 High 900rpm 81
16 3.2 to 3.4 51 to 53 2 to 4 High 900rpm 85
2 units
07 07 2.1 to 2.3 36 to 38 2 to 4 High 900rpm 70
10 07 2.1 to 2.3 36 to 38 2 to 4 High 900rpm 72
10 10 2.1 to 2.3 36 to 38 2 to 4 High 900rpm 74
13 07 2.1 to 2.3 36 to 38 2 to 4 High 900rpm 75
13 10 2.1 to 2.3 36 to 38 2 to 4 High 900rpm 75
16 07 2.0 to 2.2 34 to 36 2 to 4 High 900rpm 75
16 10 2.0 to 2.2 32 to 34 2 to 4 High 900rpm 75
13 13 2.0 to 2.2 34 to 36 2 to 4 High 900rpm 75
16 13 2.0 to 2.2 32 to 34 2 to 4 High 900rpm 75
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m × 2 units