Item Operation ow and applicable data, etc. Description
2. Indoor fan
motor control
(Continued)
[In starting and in stability]
(Table 2) Indoor fan air flow rate (Heating)
FAN AUTO
FAN Manual
In starting
Until 12 minutes passed after operation start
When 12 to 25 minutes passed after operation start
and room temp. is 3°C or lower than set temp.
Room temp. < Set temp. –4°C
In stability
When 12 to 25 minutes passed after operation start
and room temp. is higher than (set temp. –3°C)
When 25 minutes or more passed after operation start
Room temp. r Set temp. –3.5°C
Fan speed level
WF
WE UH
WD H
WC M+
WB
WA M
W9
W8 L+
W7 L
W6 L–
W5 UL
W4
W3 SUL
W2
W1
RAS-M10PKVP-E
Fan speed Air flow rate
(rpm) (m
3
/h)
1140 640
1140 640
1070 590
980 530
900 470
850 430
810 400
710 330
710 330
650 290
650 290
650 290
650 290
560 220
420 120
RAS-M13PKVP-E
Fan speed Air flow rate
(rpm) (m
3
/h)
1200 690
1200 690
1100 610
1010 550
930 490
850 430
810 400
710 330
710 330
650 290
650 290
650 290
650 290
560 220
420 120
RAS-M16PKVP-E
Fan speed Air flow rate
(rpm) (m
3
/h)
1280 750
1280 750
1180 670
1090 610
980 530
900 470
880 450
780 380
710 330
700 320
650 290
650 290
650 290
560 220
420 120

Table of Contents