55
Wire connection
REQUIREMENT
Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
Be sure to pass the cables through the bushing of wiring connection port of the indoor unit.
Keep a margin (Approx. 100mm) on a wire to hang down the electric parts box at servicing, etc.
Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and pushing the
hooking section. (The cover of the electric parts box remains hanged to the hinge.)
Connect the indoor/outdoor connection wires to the terminal block of the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
Using the attached thermal insulation material, seal the pipe connecting port. Otherwise, dewing may be caused.
Mount the cover of the electric parts box without pinching wires.
(Mount the cover after cabling on the ceiling panel.)
P.C. board
Cover of electric
parts box
Screw
Push
Screws
Electric parts box
Hooking
section
Thermal insulation to
wiring connecting port
Adhered surface
Heat
insulator A
Notched section
Power supply
terminal block
21 3
Cord clamp
Earth screw
Heat insulator B
213
Wiring on the ceiling panel
According to the Installation Manual for the ceiling
panel, connect the connectors to the P.C. board in the
electric parts box.
Connect the sensor connector to CN201 (Blue), and
the louver motor wiring connector to CN33 (White) on
the P.C. board, respectively.
Cord clamp
CN33
CN201
Infrared signal receiver wiring
(From ceiling panel)
Louver motor wiring
(From ceiling panel)
Draw and pass the sensor lead wire upper the louver
motor wiring, and then close cover of the electric parts
box. Perform the wiring work so that the electric parts
box does not pinch the sensor lead wire.