Software A3TY07X
Page 23
November, 2019
Selection List Selections Description Note
3 DO_AUTO_SET Digital output automatically set as per DO_G setting.
4 DUST Memory location that will not effect software operation.
SERSEQDATA1 Serial input word 1.
SERSEQDATA2 Serial input word 2.
DI_EX4 Serial/digital input word 4.
SP_REF_AIN1 1
st
analog input speed reference. 25000 counts=100%
SP_REF_AIN2 2
nd
analog input speed reference. 25000 counts=100%
IM_NUMBER The number of motors connected to the drive. 10000counts=100% IM only
TENS_R1 Torque reference used for Master/Slave control. 4000counts=100%
IQ_LMT_EXT External torque current limit. 4000counts=100%
5
DUST Memory location that will not effect software operation.
SSEQ_OUT1 Drive operation sequence output word 1.
SSEQ_OUT2 Drive operation sequence output word 2.
SSEQ_OUT3 Drive operation sequence output word 3.
FLGSTS_MV1 Drive status word 1.
SEQ_DATAMV02 Drive status word 2.
VAC_FBK Input voltage feedback. 10000counts=100%
IQ_F Motor torque current feedback. 4000counts=100%
I1_F Motor Average total current feedback. 4000counts=100%
VI_POWER_FLT Output kW 1count/kW.
VI_POWER01 Output kW 1 count/0.1kW.
E1_R Motor output voltage in percent. 16384 counts=100%
FO64 Output frequency. 64counts/Hz
SP_F Speed feedback. 25000counts=100%
SP_R Total speed reference. 25000counts=100%
VF_E1_REF Volts/Hertz total output voltage reference 16384 counts=100% IM only
MAIN_VAC_F Output voltage feedback. 10000counts=100%
VI_KVA_PCT Drive output kVA percent 10000counts=100%
VI_KVA Drive output kVA 1count/kVA
VI_KVAR_PCT Drive output kVAR percent 10000counts=100%
VI_KVAR Drive output kVAR 1count/kVAR
VI_PF_PCT Drive output power factor percent 10000counts=100%
MOT_POWER_PCT Motor input power percent 10000counts=100%
VDC_F_DSP Average DC voltage feedback (Filtered). 10000counts=100%
MOT_FREQ VSD Operating Output Frequency (10counts/Hz)
MOT_VOLT VSD Output Voltage (1count/volt)
INV_U_CURR U-phase RMS motor current (10counts/A)
INV_V_CURR V-phase RMS motor current (10counts/A)
INV_W_CURR W-phase RMS motor current (10 counts/A)
LINE_VOLT VSD Input Voltage (1count/V)
LINE_POWER VSD Input Power - Calculated (1count/kW)
IM_NUMBER Percentage of FLA input (100counts/%) IM only
CS_MOTOR_CURR Programmed motor rated current (10counts/A)
CS_MOTOR_VOLT Programmed motor rated voltage (1count/V)