2.4   SERVICE WARNING! 
Do not service equipment with voltage applied! The unit can be the 
source of fatal electrical shocks! To avoid shock hazard, disconnect 
main power and control power before working on the unit. Warning 
labels must be attached to terminals, enclosure and control panel to 
meet local codes. Use Lock Out tags such as the one shown when 
servicing equipment. 
 
2.5   Mounting and Cleaning 
When drilling or punching holes in the enclosure, cover the electrical 
assembly to prevent metal filings from becoming lodged in areas which 
can cause clearance reduction or actual electrical shorts. After work is 
complete, thoroughly clean, vacuum the area, and re-inspect the unit for 
foreign material.  
2.5.1 Clearances 
Make sure there is sufficient clearance all around the unit for cooling, 
wiring and maintenance purposes. To conserve panel space, the TE 
Series –BP models were designed for close vertical clearances of only 1 
inch (25mm) on either side. A minimum horizontal clearance of 4” (100 
mm) on the top and bottom is necessary to maximize effective airflow 
and cooling. Also the unit must be installed with its heat sink ribs oriented 
vertically and running parallel to the mounting surface. Keep in mind that 
these are minimums. Wiring may require more clearance, particularly on 
the bottom. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 2.5:  TE minimum mounting clearances 
 
Starte
1" minimum (25  mm)
1" minimum (25
   mm)
4" minimum ( 100 mm )
TE Series
4" minimum ( 100 mm )