38 | Page 
 
 
 
5.6.2   Starting Mode 
The TE Series is capable of several different starting modes, but is set 
from the factory for the most common applications. A second ramp 
profile is available for use should it be required. Unless wired to do so, 
the TE Series defaults to Ramp 1. This section describes functions for 
Ramp 1, with references to function numbers that do the same thing for 
Ramp 2 (if required). Refer to Appendix 2 for a detailed description of 
the differences in Ramp Profiles and their uses. All current percentages 
are based on the Motor FLA as programmed in F001. 
 
F010 =  Ramp Profile Selection 
Factory Setting = 1 
Range = 1 – 4 
This Function selects the type of Ramp Profile desired. Ramp 
profiles can be either Voltage Ramp or Current Ramp. See 
Appendix 2 for details. Each Ramp Profile consists of 3 settings: 
Initial Torque, Ramp Time and Maximum Current Limit. Because 
there are two ramps available, there are 4 settings to cover the 
combinations of profiles possible. If you are not using the 2
nd
 
ramp, the TE Series will ignore all settings in reference to Ramp 
2. 
 
 
Ramp 1  
(Dual Ramp Input Open) 
Ramp 2  
(Dual Ramp Input Closed) 
F010 
Setting 
Ramp Profile  Ramp Profile 
1 Voltage  Voltage 
2 Current  Current 
3 Voltage  Current 
4 Current  Voltage 
Table 5.6.2:  Ramp Type selection Settings 
 
Select Voltage Ramp by setting F010 = 1 (factory default) 
When Voltage Ramp is selected,  
Set Initial Torque (Voltage) with F011 (see below) 
Set Ramp Time with F013 (see below) 
Set Maximum Current Limit with F014 (see below) 
 
Or; 
 
Select Current Ramp by setting F010 = 2 
When Current Ramp is selected, 
Set Initial Torque (Current) with F012 (see below) 
Set Ramp Time with F013 (see below) 
Set Maximum Current Limit with F014 (see below) 
 
  Note: 
When either Ramp is set to “Voltage Ramp”, the corresponding 
“Initial Torque (Current)” setting is ignored. Conversely, when set to 
“Current Ramp”, the “Initial Torque (Voltage)” is ignored. 