tarters 1
1250A
 
44 | Page 
 
 
 
Caution! 
Decel is THE OPPOSITE
 of braking. Enabling the Decel feature will make the motor take 
LONGER
 to stop than if it were simply turned off. 
 
5.6.6   Restart Delay  
The TE Series can be programmed to delay restarting upon restoration 
of line power after an outage. This allows multiple units to be 
programmed to restart at staggered times in an effort to avoid causing 
additional problems with the power supply system. Another term for this 
is “Sequential Start Delay”. 
 
F028 =  Restart Delay Time 
Factory Setting = 0 (Disabled) 
Range = 0 = Disabled (no delay), or 1 - 999 seconds 
Sets a delay time before the starter can be restarted after a 
complete loss of power. Use this if multiple motors are 
connected to a supply system that may have trouble providing 
adequate power to restart them all at the same time. By using 
different Restart Delay Times on each unit, a sequential restart 
can be achieved. 
 
  Note: 
This is similar to the Coast Down Lockout Timer in F048, however it 
only activates on Power Loss. 
 
 
 